5.0 START-UP AND CONTROL PANEL
Code
Description
Reset
Action
Delay
AL173
Circuit 1 - High pressure alarm by pressure switch
M
Stop circuit 1
No
AL174
Circuit 1 - Low pressure alarm by pressure switch
R
Stop circuit 1
Parameter Ca19/Ca20
AL175
Circuit 1 - Overload compressor 1
M
Stop compr.1 Circ.1
No
AL176
Circuit 1 - Overload compressor 2
M
Stop compr.2 Circ.1
No
AL177
Circuit 1 - Overload compressor 3
M
Stop compr.3 Circ.1
No
AL178
Circuit 1 - Pump-Down end for maximum time
A
Stop circuit 1
Parameter B035
AL200
Circuit 2 - Alarm discharge probe pressure
A
Stop circuit 2
10s
AL201
Circuit 2 - Alarm suction probe pressure
A
Stop circuit 2
10s
AL202
Circuit 2 - Alarm discharge probe temperature
A
Stop circuit 2
10s
2)
AL203
Circuit 2 - Alarm suction probe temperature
A
Stop circuit 2
10s
AL205
Circuit 2 Envelope - High compression ratio
A
Stop circuit 2
Parameter Cb17
AL206
Circuit 2 Envelope - High discharge pressure
M
Stop circuit 2
Parameter Cb17
AL207
Circuit 2 Envelope - High motor current
A
Stop circuit 2
Parameter Cb17
AL208
Circuit 2 Envelope - High suction pressure
A
Stop circuit 2
Parameter Cb17
AL209
Circuit 2 Envelope - Low compression ratio
A
Stop circuit 2
Parameter Cb17
AL210
Circuit 2 Envelope - Low differential pressure
A
Stop circuit 2
Parameter Cb18
AL211
Circuit 2 Envelope - Low discharge pressure
A
Stop circuit 2
Parameter Cb17
AL212
Circuit 2 Envelope - Low suction pressure
A
Stop circuit 2
Parameter Cb17
AL213
Circuit 2 Envelope - High discharge temperature
A
Stop circuit 2
Parameter Cb17
AL214
Circuit 2 EVD - Low SH
M
Stop circuit 2
Parameter B024
AL215
Circuit 2 EVD - LOP
A
Stop circuit 2
Parameter B025
AL216
Circuit 2 EVD - MOP
A
Stop circuit 2
Parameter B026
AL217
Circuit 2 EVD - High condensing temperature
A
Stop circuit 2
Parameter B029
AL218
Circuit 2 EVD - Low suction temperature
A
Stop circuit 2
Parameter B031
AL219
Circuit 2 EVD - Motor error
M
Stop circuit 2
No
AL220
Circuit 2 EVD - Emergency closing
A
Stop circuit 2
No
AL221
Circuit 2 EVD - Setting out of bound
A
Stop circuit 2
No
AL222
Circuit 2 EVD - Settings range error
A
None
No
AL223
Circuit 2 EVD - Offline
A
Stop circuit 2
No
AL224
Circuit 2 EVD - Low battery
A
None
No
AL225
Circuit 2 EVD - EEPROM
A
None
No
AL226
Circuit 2 EVD - Incomplete valve closing
A
Stop circuit 2
No
AL227
Circuit 2 EVD - Firmware not compatible
A
Stop circuit 2
No
AL228
Circuit 2 EVD - Configuration error
A
Stop circuit 2
No
AL265
Circuit 2 - Alarm freeze evaporation temperature
M
Stop circuit 2
Parameter A041
AL266
Circuit 2 - Compressor 1 maintenance
A
None
Parameter Ca06
AL267
Circuit 2 - Compressor 2 maintenance
A
None
Parameter Ca08
AL268
Circuit 2 - Compressor 3 maintenance
A
None
Parameter Ca10
AL269
Circuit 2 - Alarm condensing temperature probe
A
Stop circuit 2
10s
AL270
Circuit 2 - Source fan 1 maintenance
A
None
Parameter E006
AL273
Circuit 2 - High pressure alarm by pressure switch
M
Stop circuit 2
No
AL274
Circuit 2 - Low pressure alarm by pressure switch
R
Stop circuit 2
Parameter Ca19/Ca20
AL275
Circuit 2 - Overload compressor 1
M
Stop compr.1 Circ.2
No
AL276
Circuit 2 - Overload compressor 2
M
Stop compr.2 Circ.2
No
AL277
Circuit 2 - Overload compressor 3
M
Stop compr.3 Circ.2
No
AL278
Circuit 2 - Pump-Down end for max time
A
Stop circuit 2
Parameter B035
(1) In case of single evaporator/condenser pump, also the
“
alarm evaporator/condenser pumps
” (AL016/017)
is activated. In case of double
evaporator/condenser pump, the latter is activated only when both
“
overload pump alarm
” (AL008
-009/AL010- 011) are simultaneously active.
(2) In the case of sensor NTC-HT, the alarm probe disconnected or below the value 0.0°C is given 60s after switching on the compressor.
Reset:
A: automatic reset
M: manual reset
R: automatic reset with retries
For further details, consult the
“
c.pCO
” microprocessor system’s special manual
o
r contact the Manufacturer of the equipment’s Technical
Assistance Office.
Finally, we wish to stress the delicate nature of the operations carried out on the machine. It is necessary to use highly qualified members of
staff to avoid causing serious damage.