Hub van Doorneweg 8 • 2171 KZ Sassenheim – NL •
T
+31(0)252 228850 •
F
+31(0)252 228235 •
E
sales@euronorm.nl •
I
euronormdrives.com
Hub van Doorneweg 8 • 2171 KZ Sassenheim – NL •
T
+31(0)252 228850 •
F
+31(0)252 228235 •
E
sales@euronorm.nl •
I
euronormdrives.com
6
7
EURN010000_
002_C
EURN010000_
002_C
Items
Specifications
Pr
otection function
Inverter protection
Overvoltage protection, undervoltage protection, overcurrent protection, overload protection, overheat
protection, overcurrent stall protection, overvoltage stall protection, losting-phase protection (Optional),
communication error, PID feedback signal abnormalities, and short circuit to ground protection.
Display
LED display
keyboard
Running
information
Monitoring objects including: Running frequency, set frequency, bus voltage, output voltage, output current,
output power, output torque, input terminal status, output terminal status, analog AI1 value , motor Actual
running speed ,PID set value percentage, PID feedback value percentage.
Error
information
At most save three error message, and the time, type, voltage, current, frequency and work status can be
queried when the failure is occurred.
Key lock and function
selection
Lock part or all of keys, define the function scope of some keys to prevent misuse.
IGBT temperature
Display current IGBT temperature inside the inverter.
Communication
RS485
Built-in 485
Envir
onment
Environment temperature
-10~40
℃
(The environment temperature in 40~50
℃
, please derating use)
Storage temperature
-20~65
℃
Environment humidity
Less than 90% R.H, no condensation.
Vibration
Below 5.9m/s² (= 0.6g)
Application sites
Indoor where no sunlight or corrosive, explosive gas and water vapor, dust, flammable gas, oil mist, water
vapor, drip or salt, etc.
Altitude
Use below 1000m without derating, 1% for each 100m increasing above 1000m, the highest altitude is 3000m
Protection level
IP20
Pr
oduct
standar
d
Product adopts safety
standards.
IEC61800-5-1:2007
Product adopts EMC
standards.
IEC61800-3:2005
Cooling method
Forced air cooling
Installation method
Rail mounting, wall mounting