Hub van Doorneweg 8 • 2171 KZ Sassenheim – NL •
T
+31(0)252 228850 •
F
+31(0)252 228235 •
E
sales@euronorm.nl •
I
euronormdrives.com
10
11
NEURN030000_220_A
NEURN030000_220_A
Items
Specifications
Running
Input signal
Running method
Keyboard/terminal/communication
Frequency setting
10 frequency settings available, including adjustable DC(0
~
10V/-
10
~
+10V), adjustable DC(0~20mA), panel potentiometer, etc.
Start signal
Rotate forward/reverse
Multi-speed
At most 16-speed can be set(Run by using the multi-function terminals
or program)
Emergency stop
Interrupt controller output
Wobbulate run
Process control run
Fault reset
When the protection function is active, you can automatically or
manually reset the fault condition.
PID feedback signal
Including DC(0~10V), DC(0~20mA)
Output Signal
Running status
Motor status display, stop, ac/deceleration, constant speed, program
running status.
Fault output
Contact capacity :normally closed contact 3A/AC 250V,normally open
contact5A/AC 250V,1A/DC 30V.
Analog output
Two-way analog output, 16 signals can be selected such as frequency,
current, voltage and other, output signal range (0~10V / 0~20mA).
Output signal
At most 4-way output, there are 40 signals each way
Run function
Limit frequency, jump frequency, frequency compensation, auto-tuning,
PID control
DC current braking
Built-in PID regulates braking current to ensure sufficient braking torque
under no overcurrent condition.
Running command channel
Three channels: Operation panel, control terminals and serial
communication port. They can be switched through a variety of ways.
Frequency source
Total 10 frequency sources: Digital, analog voltage, analog current,
multi-speed and serial port. They can be switched through a variety of
ways.
Input terminals
8 digital input terminals, compatible with active PNP or NPN input
mode, one of them can be for high-speed pulse input(0~100 kHz
square wave); 3 analog input terminals for voltage or current input.
Output terminals
2 digital output terminals, one of them can be for high-speed pulse
output(0~100kHz square wave); one relay output terminal; 2 analog
output terminals respectively for optional range (0~20mA / 0~10V),
they can be used to set frequency, output frequency, speed and other
physical parameters.
Pr
otection function
Inverter protection
Overvoltage protection, undervoltage protection, overcurrent protection,
overload protection, overheat protection, overcurrent stall protection,
overvoltage stall protection, losting-phase protection (Optional),
communication error, PID feedback signal abnormalities, PG failure and
short circuit to ground protection.
IGBT temperature display
Displays current temperature IGBT
Inverter fan control
Can be set
Instantaneous power-down restart
Less than 15 milliseconds: Continuous operation.
More than 15 milliseconds: Automatic detection of motor speed,
instantaneous power-down restart.
Speed start tracking method
The inverter automatically tracks motor speed after it starts
Parameter protection function
Protect inverter parameters by setting administrator Password and
decoding
Display
LED/OLED display keyboard
Running
information
Monitoring objects including: Running frequency, set frequency, bus
voltage, output voltage, output current, output power, output torque,
input terminal status, output terminal status, analog AI1 value, analog
AI2 value, motor Actual running speed,PID set value percentage, PID
feedback value percentage.
Error message
At most save three error message, and the time, type, voltage, current,
frequency and work status can be queried when the failure is occurred.
LED display
Display parameters
OLED display
Optional, prompts operation content in Chinese/English text.
Copy parameter
Can upload and download function code information of frequency
converter, rapid replication parameters.
Key lock and function selection
Lock part or all of keys, define the function scope of some keys to
prevent misuse.