5.5.2 The way to read parameters in various status
In stop or run status, operate shift key
SHIFT
to display a variety of status parameters respectively. Parameter display
selection depends on function code F6.01 (Run parameter 1), F6.02 (Run parameter 2) and F6.03 (Stop parameter 3).
In stop status, there are total 16 stop status parameters that can be set to display/not display: Set frequency, bus voltage,
DI input status, DO output status, analog input AI1 voltage, analog input AI2 voltage, panel potentiometer input voltage,
Actual count value, Actual length value, PLC running step number, Actual speed display, PID settings, high-speed pulse
input frequency and reserve, switch and display the selected parameter by pressing key orderly.
In running status, there are 5 running-status parameters:running frequency,setting frequency,bus voltage,output voltage,
output current default display, and other display parameters: Output power, output torque, DI input status, DO output
status, analog input AI1 voltage, analog input AI2 voltage, panel potentiometer input voltage, Actual count value, Actual
length value, linear speed, PID settings and PID feedback, etc, their display depends on function code F6.01 and F6.02
switch and display the selected parameter by pressing key orderly.
Inverter powers off and then powers on again, the displayed parameters are the selected parameters before power-off.
5.5.3 Password settings
The inverter has password protection. When y0.01 become not zero, it is the password and will be work after exit from
function code modified status. Press PRG key again, will display”----”. One must input the correct password to go to
regular menu, otherwise, inaccessible.
To cancel the password protection function, firstly enter correct password to access and then set y0.01 to 0.
3.5.4 Motor parameter auto turning
Choose vector control, one must input the motor’s parameters in the nameplate accurately before running the inverter.
JI500 series frequency inverter will match the motor’s standard parameters according to its nameplate. The vector control
is highly depend on motor’s parameters. The parameters of the controlled motor must be inputted accurately for the good
control performance.
Motor parameter auto tunning steps are as follows:
Firstly select command source (F0.11=0) as the comment channel for operation panel, then input the following
parameters according to the actual motor parameters (Selection is based on the current motor):
Motor Selection
Parameters
Motor
b0.00: Motor type selection b0.03: Motor rated current
b0.01: Motor rated power
b0.04: Motor rated frequency
b0.02: Motor rated voltage
b0.05: Motor rated speed
For asynchronous motors
If the motor can NOT completely disengage its load, please select 1 (asynchronous motor parameter static auto turning)
for b0.27, and then press the RUN key on the keyboard panel.
If the motor can completely disengage its load, please select 2 (asynchronous motor parameter comprehensive auto
turning) for b0.27, and then press the RUN key on the keyboard panel, the inverter will automatically calculate the motor’s
following parameters:
Motor Selection
Parameters
Motor
b0.06: Asynchronous motor stator resistance
b0.09:Asynchronous motor mutual inductance
b0.07: Asynchronous motor rotor resistance
b0.10:Asynchronous motor no-load current
b0.08: Asynchronous motor leakage inductance
Complete motor parameter auto turning