Hub van Doorneweg 8 • 2171 KZ Sassenheim – NL •
T
+31(0)252 228850 •
F
+31(0)252 228235 •
E
sales@euronorm.nl •
I
euronormdrives.com
36
37
NEURN030000_220_A
NEURN030000_220_A
F2.12
Expansion card DO output delay time
0.0s~3600.0s
0.0s
☆
F2.13
SPA output delay time
0.0s~3600.0s
0.0s
☆
F2.14
Relay 2 output delay time
0.0s~3600.0s
0.0s
☆
F2.15
DO output terminal active status selection
Units digit:
SPB switching quantity
0: Positive logic; 1: Anti-logic
Tens digit: Relay 1
Hundreds digit: Hundreds digit: Undefined
Thousands digit: SPA
Ten thousands digit: Relay 2
00000
☆
F2.16
DA1 zero bias coefficient
-100.0% ~ +100.0%
0.0%
☆
F2.17
DA1 gain
-10.00 ~ +10.00
1.00
☆
F2.18
DA2 zero bias coefficient
-100.0% ~ +100.0%
20.0%
☆
F2.19
DA2 gain
-10.00 ~ +10.00
0.80
☆
7.1.5 F3 Group - Start and stop control group
Code
Parameter name
Setting range
Factory
setting
Change
F3.00
Start-up mode
0: Direct startup
1: Speed tracking restart
2: Pre-excitation start (AC asynchronous motor)
0
☆
F3.01
Speed tracking mode
0~2: Reserve
3: Rotate speed tracking method3
3
★
F3.02
Speed tracking value
1~100
20
☆
F3.03
Start frequency
0.00Hz~10.00Hz
0.00Hz
☆
F3.04
Hold time for start frequency
0.0s~100.0s
0.0s
★
F3.05
DC beforehand field current
0%~100%
0%
★
F3.06
DC excitation time beforehand
0.0s~100.0s
0.0s
★
F3.07
Stop mode
0: Deceleration parking 1: Free stop
0
☆
F3.08
DC Initial frequency
0.00Hz~F0.19 (Maximum frequency)
0.00Hz
☆
F3.09
DC Waiting time
0.0s~100.0s
0.0s
☆
F3.10
Stop DC braking current
0%~100%
0%
☆
F3.11
Stop DC braking time
0.0s~100.0s
0.0s
☆
F3.12
Braking utilization rate
0%~100%
100%
☆
F3.13
Ac/deceleration mode
0: Linear acceleration and deceleration
1:S curve acceleration and deceleration A
2:S curve acceleration and deceleration B
0
★
F3.14
Proportion of S curve start-section
0.0%~(100.0%to F3.15)
30.0%
★
F3.15
Proportion of S curve end-section
0.0%~(100.0%~F3.14)
30.0%
★
7.1.6 F4 Group - V/F control parameters
Code
Parameter name
Setting range
Factory
setting
Change
F4.00
V/F curve setting
0: Linear V/F,Suitable for ordinary constant torque
load.
1: Multi-point V/F,Suitable for dehydrator, centri-
fuge and other special loads any V/F relationship
curves can be obtained by setting parameters
F4.03~F4.08.
2: Square V/F,Suitable for fans, pumps and cen-
trifugal loads.
3~8: V/F relationship curve between linear V/F and
square V/F.
0
★
F4.01
Torque boost
0.0%(Automatic torque boost) 0.1~30%
0.0%
★