38
39
NEURN030000_220_A
NEURN030000_220_A
F4.02
Torque boost cut-off frequency
0.00Hz~F0.19(Maximum frequency)
15.00Hz
★
F4.03
MultipointV/F frequency point 1
0.00Hz~F4.05
-
★
F4.04
Multipoint V/F voltage point 1
0.0%~100.0%
-
★
F4.05
Multipoint V/F frequency point 2
F4.03~F4.07
-
★
F4.06
Multipoint V/F voltage point 2
0.0%~100.0%
-
★
F4.07
Multipoint V/F frequency point 3
F4.05~b0.04 (Rated motor frequency)
-
★
F4.08
Multipoint V/F voltage point 3
0.0%~100.0%
-
★
F4.09
Slip compensation coefficient
0%~200.0%
0.0%
☆
F4.10
Overexcitation gain
0~200
80
☆
F4.11
Oscillation suppression gain
0~100
0
☆
F4.12
V/F separation voltage source
0~9
0
☆
F4.13
V/F separation voltage digital setting
0V~rated motor voltage
0V
☆
F4.14
V/F separation voltage rise time
0.0s~1000.0s
0.0s
☆
F4.15
V/F automatic torque lifting KP
0~100
56
☆
F4.16
V/F automatic torque lifting ki
0~100
49
☆
F4.17
V/F automatic torque raising Max
0~2000
1228
☆
F4.18
V/F automatic torque raising min
0: Determined by power;
1: Changed manually
0
☆
F4.19
V/F automatic torque lifting adjustment
0~200%
100%
☆
F4.20
AVR automatic voltage regulation
0: Enable;
1: Not enable
0
☆
5.1.7 F5 Group - Vector control parameters
Code
Parameter name
Setting range
Factory
setting
Change
F5.00
Speed loop ratio G1
1~100
30
☆
F5.01
Speed loopintegral T1
0.01s~10.00s
0.50s
☆
F5.02
switching frequency 1
0.00~F5.05
5.00Hz
☆
F5.03
Speed loop ratio G2
0~100
20
☆
F5.04
Speed loop integral T2
0.01s~10.00s
1.00s
☆
F5.05
Switching frequency 2
F5.02~F0.19(Max. Frequency)
10.00Hz
☆
F5.06
Speed loop integral
0: Invalid 1: Valid
0
☆
F5.07
Torque limit upper limit source
0: Function code F5.08 setting
1: AI1
2: AI2
3: Panel potentiometer setting
4: High-speed pulse setting
5: Communication setting
6: Min(AI1, AI2)
7: Max(AI1, AI2)
8: AI3 setting
0
☆
F5.08
Upper limit digital setting for torque
0.0%~200.0%
150.0%
☆
F5.09
Vector control differential gain
50%~200%
150%
☆
F5.10
Speed loop filter time constant
0.000s~0.100s
0.000s
☆
F5.11
Vector control overexcitation gain
0~200
64
☆
F5.12
Excitation regulator proportional gain
0~60000
2000
☆
F5.13
Excitation regulator integral gain
0~60000
1300
☆
F5.14
Torque regulator proportional gain
0~60000
2000
☆
F5.15
Torque regulator integral gain
0~60000
1300
☆