40
41
NEURN030000_220_A
NEURN030000_220_A
5.1.9 F7 Group - Auxiliary function group
Code
Parameter name
Setting range
Factory
setting
Change
F7.00
Jog running frequency
0.00Hz~F0.19(Maximum frequency)
2.00Hz
☆
F7.01
Jog acceleration time
0.0s~6500.0s
20.0s
☆
F7.02
Jog deceleration time
0.0s~6500.0s
20.0s
☆
F7.03
Jog priority
0:Invalid 1: Valid
1
☆
F7.04
Jump frequency 1
0.00Hz~F0.19 (Maximum frequency)
0.00Hz
☆
F7.05
Jump frequency 2
0.00Hz~F0.19(Maximum frequency)
0.00Hz
☆
F7.06
Jump frequency range
0.00Hz~F0.19 (Maximum frequency)
0.00Hz
☆
F7.07
Jump frequency availability during ac/
deceleration process
0: Invalid 1: Valid
0
☆
F7.08
Acceleration time 2
0.0s~6500.0s
Depends on
models
☆
F7.09
Deceleration time 2
0.0s~6500.0s
Depends on
models
☆
F7.10
Acceleration time 3
0.0s~6500.0s
Depends on
models
☆
F7.11
Deceleration time 3
0.0s~6500.0s
Depends on
models
☆
F7.12
Acceleration time 4
0.0s~6500.0s
Depends on
models
☆
F7.13
Deceleration time 4
0.0s~6500.0s
Depends on
models
☆
F7.14
Switching frequency point between
acceleration time 1 and acceleration time 2
0.00Hz~F0.19 (Maximum frequency)
0.00Hz
☆
F7.15
Switching frequency point between
deceleration time 1 and deceleration time 2
0.00Hz~F0.19 (Maximum frequency)
0.00Hz
☆
F7.16
Forward/reverse rotation deadband
0.00s~3600.0s
0.00s
☆
F7.17
Reverse rotation control
0: Enable 1: Disable
0
☆
F7.18
Set frequency lower than lower limit frequency
mode
0: Running at lower limit frequency
1: Stop
2: zero speed running
0
☆
F7.19
Droop control
0.00Hz~10.00Hz
0.00Hz
☆
F7.20
Setting cumulative power-on arrival time
0h~36000h
0h
☆
F7.21
Setting cumulative running arrival time
0h~36000h
0h
☆
F7.22
Start protection selection
0: OFF 1: ON
0
☆
F7.23
Frequency detection value (FDT1)
0.00Hz~F0.19(Maximum frequency)
50.00Hz
☆
F7.24
Frequency detection hysteresis value (FDT1)
0.0%~100.0% (FDT1 level)
5.0%
☆
F7.25
Frequency reaches detection width
0.00~100% (Maximum frequency)
0.0%
☆
F7.26
Frequency detection value (FDT2)
0.00Hz~F0.19 (Maximum frequency)
50.00Hz
☆
F7.27
Frequency detection hysteresis value (FDT2)
0.0%~100.0% (FDT2 level)
5.0%
☆
F7.28
Random arrivals frequency detection value 1
0.00Hz~F0.19 (Maximum frequency)
50.00Hz
☆
F7.29
Random arrivals frequency detection width 1
0.00%~100.0% (Maximum frequency)
0.0%
☆
F7.30
Random arrivals frequency detection value 2
0.00Hz~F0.19 (Maximum frequency)
50.00Hz
☆
F7.31
Random arrivals frequency detection width 2
0.00%~100.0% (Maximum frequency)
0.0%
☆
F7.32
Zero current detection level
0.0%~300.0% (Rated motor current)
5.0%
☆
F7.33
Zero current detection delay time
0.01s~360.00s
0.10s
☆
F7.34
Overrun value of output current
0.0% (Not detected)
0.1%~300.0% (Rated motor current)
200.0%
☆
F7.35
Output current overrun detection delay time
0.00s~360.00s
0.00s
☆
F7.36
Random arrivals current 1
0.0%~300.0% (Rated motor current)
-100.0%
☆
F7.37
Random arrivals current 1 width
0.0%~300.0% (Rated motor current)
0.0%
☆
F7.38
Random arrivals current 2
0.0%~300.0% (Rated motor current)
-100.0%
☆
F7.39
Random arrivals current 2 width
0.0%~300.0% (Rated motor current)
0.0%
☆
F7.40
Module temperature arrival
0 °C~100°C
75°C
☆