42
43
NEURN030000_220_A
NEURN030000_220_A
F8.17
Fault protection action selection 1
Units digit: Motor overload (Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss (Err.12)
(Same as units digit)
Hundred digit: Output phase loss (Err.13)
(Same as units digit)
Thousand digit: External fault (Err.15)
(Same as units digit)
Ten thousands digit: Communication abnormal
( Err.16)(Same as units digit)
00000
☆
F8.18
Fault protection action selection 2
Units digit: Encoder fault(Err.20)
0: Free stop
1:Switch to V/F and then stop at the selected
mode
2: Switch to V/F and continue to run
Tens digit: function code read and write abnormal
(Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor overheating (Err.45)
(Same as F8.17 units digit)
Ten thousands digit: Running time arrival (Err.26)
(Same as F8.17 units digit)
00000
☆
F8.19
Fault protection action selection 3
Units digit:User-defined fault 1(Err.27)
(Same as F8.17 units digit)
Tens digit:User-defined fault 2(Err.28)
(Same as F8.17 units digit)
Hundreds digit: Power-on time arrival (Err.29)
(Same as F8.17 units digit)
Thousands digit: Reserved
Ten thousands digit: PID feedback loss when
running (Err.31) (Same as F8.17 units digit)
00000
☆
F8.20
Fault protection action selection 4
Units digit: Too large speed deviation (Err.42)
(Same as F8.17 units digit)
Tens digit: Motor over-speed (Err.43)
Hundreds digit: Initial position error (Err.51)
(Same as F8.17 units digit) Thousands digit:
Reserved Ten thousands digit: Reserved
00000
☆
F8.21~ F8.23 Reserve
F8.24
Fault running frequency
0: Current frequency running
1: Setting frequency running
2: Upper frequency running
3: Down frequency running
4: Abnormal reserve frequency running
0
☆
F8.25
Abnormal reserve frequency
60.0%~100.0%
90%
☆
F8.26
Momentary power cut action selection
0: Invalid
1: Deceleration
2: Deceleration and stop
0.50s
☆
F8.27
Reserved
F8.28
Recovery voltage judgment time of momentary
power cut
0.00s~100.00s
0
☆
F8.29
Judgment voltage of momentary power cut
action
50.0%~100.0% (Standard bus voltage)
10%
☆
F8.30
Load drop protection selection
0: Invalid 1: Valid
1.0s
☆
F8.31
load drop detection level
0.0~100.0%
0
☆
F8.32
Load drop detection time
0.0~60.0s
110
☆
F8.33
Motor temperature sensor type
0: Invalid; 1: PT100 detect
0
☆
F8.34
Motor over heat protection value
0~200
110
☆
F8.35
Motor over heat alma value
0~200
90
☆
F8.36
Start short circuit protection
0: Enable; 1: Not enable
0
☆
F8.37
Holzer detection
0: Two way hall; 1: Three way Hall
0
☆
F8.38
Three way hall operation short circuit to ground
threshold
0~100% (Relative motor current)
8%
☆