F9.04
Communication time out
Factory value
0.0 s
Response delay
0.0s (invalid) ; 0.1~60.0s
When the function code is set to 0.0s, the communication timeout time parameter is invalid.
When the function code is set to a valid value, the system will report the fault fault (Fault sequence number Err.16) if the
communication time between the next communication and the next communication time exceeds the communication
time. Usually, they are set to invalid. If you are in a continuous communication system, set the secondary parameters,
you can monitor the status of the communication.
F9.05
Communication protocol selection
Factory value
1
Response delay
0: Non standard Modbus protocol;
1: Standard Modbus protocol
F9.05 = 1: Select standard Modbus protocol.
F9.05 = 0: Read command, the return of the number of bytes from the machine is more than one byte of the standard
Modbus protocol.
F9.06
Communication read current resolution
Factory value
0
Response delay
0:0.01A; 1:0.1A
The output unit of the current value is used to determine the output current of the communication read output.