background image

Page 18

DV 42 Indoor Gas Fireplace

Installation

Section 6:  Finishing

Figure 24.

 Combustible mantels and facings.

Finishing Around the Fireplace
Combustible mantels and mouldings may be safely installed 

over the top and on the front of the fireplace provided that 

they do not project beyond shaded area shown in Figure 24.
Fireplace Facing
When sizing the finish material for your fireplace, it is important 

to  remember  the  following:  THE  OPENING  MUST  NOT  BE 

OBSTRUCTED IN ANY WAY - to do so restricts the air supply for 

the control compartments and heat exchanger it also prevents 

access for servicing controls.
The face of the fireplace may be painted to match the room 

decor, provided you use a heat-resistant paint.  Decorative facing 

must not extend past the fireplace opening at all, because it will 

interfere with the access to retainers for removal of glass door.

Top of fireplace

Non-Combustible

Combustible Facing 

Material

Facing Material

Combustible

Construction allowed 

in shaded area

  Steel Stud construction allowable

within the grey-out area

Horizontal Run (in.)

Vertical Height (in.)

Figure 24a.

  

Installing the Nailing Flange Extension.

Installing the Nailing Flange Extension

 

 

Once the fireplace is placed into the rough framed opening, 

and the supplied steel lintel is in place, (Part No. L38087) (see

 

Figure 2

), 

What is Combustible?

Materials  that  can  catch  fire  and  burn  are  considered 

combustible. Any material that is made of, or faced with, wood, 

wood pulp, paper, plastic or any other material that can catch 

fire and burn is considered combustible. Even though these 

materials may have been 'flame-proofed', made 'fire-resistant' 

or are 'fire-rated' they are considered combustible. 
The combustibility of a material can be tested per "ASTM E136 

Standard Test Method for Behavior of Materials in a Vertical Tube 

Furnace at 750 Degrees C".  Note that 'fire-resistant' does NOT 

mean non-combustible.
Note: If a certain material has a core considered to be non-

combustible (in accordance with ASTM E136) but is faced with 

a combustible material then the material is considered to be 

combustible. 
When in doubt, ask for an ASTM E136 compliance statement.

What is Non-combustible?

A given material is said to be non-combustible when it cannot 

catch fire and burn. For example, materials made entirely, or 

in combinations, of, stone, brick, concrete, tile, steel, plaster or 

glass are considered non-combustible.
For the purposes of the installations described in this Manual, 

those  materials  that  have  passed  the  ASTM  E136  tests  are 

considered to be non-combustible.
As of this writing, the materials listed below are reported by 

their  manufacturers  to  be  non-combustible  (in  accordance 

with ASTM E136):

• 

James Hardie Building Products, Inc.: 

 HardieBacker™ 1/4” Cement Board

• 

U.S. Architectural Products, Inc.: 

 Versaroc® Cement Bonded Particle  Board 

Cem-Clad® Cement Panel

Summary of Contents for DV 42

Page 1: ...anger for cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical radiation Non ionizing radiation Radiation Hazardous to the Environment Danger of harming your hands Irritant Cutting Watch your step Slippery floor High temperatures Glass hazard Danger of suffocation High voltage Toxic Flammable materials Corrosive Fork lift trucks Danger overhead crane...

Page 2: ... 11 Top Vent Wall mounted termination one elbow 11 Top Vent Wall mounted termination multi elbow 11 Top Vent Wall mounted termination 45 corner 12 Top Vent Wall mounted termination 45 corner 12 Rear Vent Wall mounted Termination Graph 13 Standard Rear Vent no elbows or offsets 13 Rear Vent Wall mounted termination two elbows 13 Section 3 3 2 Venting Components 14 Section 3 3 3 Heat Shields 15 Inst...

Page 3: ...g body where the fireplace is being installed This installation operation and maintenance manual is applicabletothemodelsdescribedbelow Refertoyourrating plate to verify included options TheEuropeanHomewarrantywillbevoidedby andEuropean Home disclaims any responsibility for the following actions Modification of the fireplace and or components including direct vent assembly or glass doors Use of an...

Page 4: ...6 XW2018 Due to high operating temperatures this appliance should be located out of traffic away from furniture and draperies Children and adults should be alerted to the hazards of the high surface temperature which could cause burns or clothing ignition Young children should be carefully supervised when they are in the same room as the appliance Clothing or other flammable materials should not b...

Page 5: ...y be installed in any location that maintainsproperclearancestoairconditioningducts electrical wiringandplumbing Safety aswellasefficiencyofoperation shouldbeconsideredwhenselectingthefireplacelocation Try toselectalocationthatdoesnotinterferewithroomtraffic has adequate ventilation and offers an accessible path for direct vent installation The fireplace dimensions are shown below 6 5 19 Opening 3...

Page 6: ...e fireplace top vent Figure 4 Combustible framing for rear vent with shelf above the fireplace Figure 3 Combustible framing for top vent with shelf above fireplace European Home supplies a variety of direct venting and termination options The direct vent termination location MUSTbeselectedsuchthatitisthehighestpointintheventing assembly It should also be selected such that it provides the shortest...

Page 7: ... refer to the appropriate section below for installation details All fireplaces shipped from the factory are top vent See Section 3 1 for converting the unit from top vent to rear vent Figure 6 CombustibleFramingSideHeatShield twopieces Framing Heat Shield Included with the DV 42 Gas fireplace is a framing heat shield kit This kit is fabricated from galvanized steel and arrives with three pieces a...

Page 8: ...ir inlet Termination location must be a minimum 18 from a parapet wall A maximum of two offsets each offset is made up of two 90 bends may be made Install a firestop at any location where venting passes through combustible materials and construction Utilize support straps or support plates and rings as required to meet acceptable building practices Install all roof flashing and storm collars as sh...

Page 9: ...of vent runs and 2 above horizontal vent runs to any combustible material Ensurewhencuttingsectionsofrigidpipetomaintain integrity of internal supports Place the springs supplied with the pipe kit between the outer and inner pipes to keep the pipes separate and avoid any possible hot spots EuropeanHomerecommendstheuseofaflexsection for the final pipe connected directly to the fireplace offeringgre...

Page 10: ... the BSR opening to 12 x 12 2 Secure the BSR frame to the exterior sheathing of the structure 3 FastentheterminationtotheBSRframeusingaminimumof4screws 1 Frame the MOSR opening to 12 x 12 2 FastentheMOSRframetotheinteriorsideofthestuds concrete or finished wall construction using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here from the inside and attach to the MOSR...

Page 11: ... one 90 bend The vent run must comply with Venting Graph for Top Vent wall mounted terminations Figure 14 Figure16a TopVented wallmountedmulti elbowinstallation See VentingGraphforTopVent wallmountedterminations Figure14 Important Aninspectionoftheexplosionreliefflappersanddoormust be made prior to lighting the fireplace This will ensure the door gasket material will provide an adequate seal durin...

Page 12: ...on 45 or less Corner Installation Use an PTO 4 termination and an PFL 1 or PFL 2 PFL 2 12 or 24 compressed length and a frame if appropriate Flex may be turned to obtain desired degree of angle required but must not exceed 45 Note A wall venting kits is available for both the straight and the corner installation The kit includes a heat shield a PXT 12 and a termination with a mounting frame PEL 45...

Page 13: ...cceptable Example A Acceptable Installation If the vertical dimension from the hearth is 120 and the horizontalruntothewallflangeoftheventterminationis138 then the vent configuration is acceptable Example B Unacceptable Installation Iftheverticaldimensionfromthehearthis48 andthehorizontal run to the wall flange of the vent termination is 72 then the vent configuration is NOT acceptable Example C U...

Page 14: ...n European Home parts will void the warranty and may impede operation of the fireplace Use any combination of rigid and flex pipe as required Flex sections may be stretched up to 50 of their total length e g a 24 section maybe stretched to 36 Connectallventsectionsusingaminimumofthreesheet metal screws on the outer pipe flue Ensure the pipe ends male to female slide in a minimum of 11 2 of overlap...

Page 15: ...ng the outer section in place Termination Drywall sheetrock RHS101 Heat Shield inner Section RHS101 Heat Shield Outer Section Fireplace Installing aWall Mounted RHS101 Heat shield The RHS101 Heat shield MUST be used where the RHS8 Termination Figure 19 and 19a CANNOT be used Use the RHS101whereanyofthedimensionsarewithintheparameters shown Figure 19a To install the RHS101 slide the inner section o...

Page 16: ...C22 1 Canadian Electrical Code Part 1 and or Local Codes InstallationsintheUSAwhichemploythefansmustbegrounded inaccordancewithlocalcodesor intheabsenceoflocalcodes with the National Electrical Code ANSI NFPA 70 1987 FormoreinformationseetheFanKitInstallationGuideincluded with the fan kit NOTE If any of the original wire supplied with the appliance is replaced it must be replaced with the same typ...

Page 17: ...performancerequiresproperinput pressures Gas line sizing requirements will be determined in ANSI Z221 3 National Fuel Gas Code in the USA and CAN CGA B149 in Canada Pressure requirements are Gas Pressure Natural Gas Propane Minimum inlet pressure 5 5in w c 11in w c Manifold pressure 3 5in w c 10in w c The manifold outlet pressure is set from the factory to the appropriate pressure but should be ve...

Page 18: ...mbustible Materials that can catch fire and burn are considered combustible Anymaterialthatismadeof orfacedwith wood wood pulp paper plastic or any other material that can catch fire and burn is considered combustible Even though these materials may have been flame proofed made fire resistant or are fire rated they are considered combustible The combustibility of a material can be tested per ASTM ...

Page 19: ...Figure 26b Door Buckle Tool 1 Step 4 Firmlygrasphand hold end of door buckle tool andplacethemachined end in the slot under door frame as shown Figure 26c Step 2 Step 3 Step 1 Removethehorizontalcover by placing fingers in both finger holes then pushing away from you and lifting out Place it aside during maintenance or cleaning Install in reverse order Installed Gas Valve Cover Finger Holes The su...

Page 20: ...r hook the top edge of the door frame into place Lower the door into position and follow the previous steps shown in reverse order Installing the Door 2 Step 5 Ensure the tool is firmly in the lower end of the slot as shown then pull toward you CAUTION Hold the tool securely 3 Step 6 Pull hard if necessary to release the spring tension CAUTION The latch springs back with force hold the tool secure...

Page 21: ...rizontal access panel withContinuous Pilot withAmericanFlameElectronicIgnition For Your Safety READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life Lighting Instructions 1 STOP Read the safety information above on this label 2 Lift out the lower horizontal access panel 3 Pushingascontrolk...

Page 22: ...cause some gas is heavier than air and will settle on the floor What To Do If You Smell Gas Do not try to light any appliance Donottouchanyelectricalswitch donotuseanyphone in your building Immediately call your gas supplier from a neighbor s 1 STOP Read the safety information above on this label 2 Remove the lower horizontal access panel 3 Turn Incoming gas valve to the ON position 4 Wait 5 minut...

Page 23: ...iodically to remove any film a normal by product of combustion which may be visible Film can easily be removed by removing the door as shown on Page 19 Handle the door carefully andcleanitwithnon abrasiveglasscleaners Oneofthe most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls ...

Page 24: ...ame Locate pilot adjustment screw on gas control valve Flame is decreased by turning adjustment screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check wiring diagram Figure 33 Main burner will not ignite 1 Check wiring see Figure 33 2 Check wall switch for proper connection Models DV 42 E Models DV 42 Replacement Par...

Page 25: ...nited States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustionairinlettoanyotherappliance 16inches 41cm minimum for appliances 100 000 BTU H 30kW M clearancetomechanicalairsupplyinlet 6feet 1 8m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearance under veranda porch deck o...

Page 26: ...ompany 2 The European Home Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood thatThe Company sole obligat...

Page 27: ...f the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GASVENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION Thestateorlocalgasinspectorofthesidewallhorizontallyventedgasfueledequipmentsha...

Page 28: ...rev 110328 EUROPEAN HOME a division of Europa Ja Inc 376 Washington St Suite 203 Malden MA 02148 tel 781 324 8383 fax 781 324 8384 www europeanhome com ...

Reviews: