background image

Page 23

DV52 Gas Fireplace

rev.101207

 

                   

                       

 

Amendment

 

 

 

  (Gas Fireplace / Equipment sold in the State of Massachusetts)

 

 

 

 

   5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device that will automatically shut off 
the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or 
operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks 
and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas 

fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the 
installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or 
structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the 
installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up 
may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above 
requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be 

ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in 

line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT 
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspec-

tor observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part 

for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manufacturer of Product Approved side wall horizontally vented 

gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the 
venting system shall include:
 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the manufacturer of a Product Approved side wall horizontally 

vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instruc-

tions. 
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all 
venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation shall be submitted to the 
Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusetts Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Appendix B - State of Massachusetts

Summary of Contents for DV 52

Page 1: ...amage Refer to this manual For assistance or additional information consult a qualifiedinstaller serviceagencyorthe gassupplier Warning What to do if you smell gas Donottrytolightanyappliance Donottouchanyelectricalswitch do notuseanyphoneinyourbuilding Immediatelycallyourgassupplier fromaneighbor sphone Followthe gassupplier sinstructions Ifyoucannotreachyourgassupplier callthefiredepartment Inst...

Page 2: ...replace 13 Mantels and Surrounds 14 Table Of Contents Wiring 14 Removing and Installing the Door 15 Operation 17 Maintenance 19 Troubleshooting 20 Spare Parts 20 Warranty 21 Appendix A Termination Locations 22 B State of Massachusetts 23 Congratulations Congratulations on selecting a European Home gas fireplace an elegant and well designed gas fireplace built with you in mind The gas fireplace you...

Page 3: ...codes with the National Electrical Code ANSI NFPA 70 1987 Within the State of Massachusetts this fireplace must comply with NFPA 54 Chapter 10 CAUTION Due to its high operating temperatures the appliance should be located out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of the high surface temperature which could cause burns or clothing igni...

Page 4: ...commended that outer walls of the chase be insulated with a vapor barrier This will reduce the possibility of a cold air convection current on the fireplace Clearances These clearances apply to all dimensions except the framed opening where the clearancestocombustiblesare0 TheDV52clearancestocombustiblematerialsare Top Rear Vent N A Top Top Vent 24 Back 3 Sides 2 Floor 0 Mantle 4 TopView FrontView...

Page 5: ...e applicable installation codes Only use gas shut off valves approved for use by the state province region or governing body in which the appliance is being installed or as required by the applicable installation codes Flexiblegasconnectorsmustnotexceed3feetinlength unlessitisallowable within applicable installation codes The appliance and its individual shut off valve must be disconnected from th...

Page 6: ...that the two long mounting brackets are facing the bottom of the termination see inset This will provide more heat protection at the top of the termination where temperatures are highest 2 Attach to the faceplate of the termination using four sheet metal screws 3 If installing the termination over vinyl siding Use theVSSTermination Shield Installing Heat Guards overTerminations Installing The Stan...

Page 7: ...er Flue Cap 8 Outer Flue Cap Flue Gasket Flue Cover Plate 8 Outer Flue Collar 5 Inner Flue Collar 5 Inner Flue Collar 8 Outer Flue Collar Flue Gasket Flue Cover Plate 5 Inner ue Cap Fl Fl 8 Outer ue Cap Figure 7a Fluecapinstallation topventedDV52fireplace Figure 7b Fluecollarinstallation topventedDV52fireplace Figure 8a Fluecapinstallation rearventedDV52fireplace Figure 8b Fluecollarinstallation r...

Page 8: ...t run must fall withinthelimitssetbytheventinggraph 90 Elbow PEXT Section Termination If the X falls on or above the top boundary of the shaded area the installation is acceptable Example A Acceptable Installation Iftheverticaldimensionfromthehearthis84 andthehorizontalruntothewallflange of the vent termination is 36 the installation is acceptable Example B Acceptable Installation Iftheverticaldim...

Page 9: ...se B Vertical Through The Roof Installations Vertical rise 12 can be reduced on applicable models Vertical terminations must be installed minimum 2 two feet above the highest point where vent passes through the roof minimum 6 six feet from a mechanical air inlet minimum 18 11 2 feet from a parapet wall Maximum vent height is 32 feet above fireplace Note Flame characteristics will change if the max...

Page 10: ...th2offsets 1offset two90 bends Figure 16 Verticalventingwith1offset 1offset two90 bends PEXT PEXT PXT 10 Figure16a RHS8Installation Installbyslidingoverventpipewhereitpassesthrough thecombustibleconstruction Figure 16b RHS101Installation Installbyslidingoverventpipewhereitpasses throughthecombustibleconstruction Framing Drywall RHS101 Heat Shield Inner Section Vent from fireplace RHS101 Heat Shiel...

Page 11: ...ptable Unacceptable venting can affect the fireplace s combustion TheVenting Graph Measuretheverticalheightfromthefireplacehearthtothecenterofthetermination andthehorizontalrunfromthefromthefireplacefluecollartothewallflangeofthe termination Plot on theVenting Graph Figure 22c with an X If the X falls on or above the top boundary of the shaded area the installation is acceptable B Multi Elbow Inst...

Page 12: ...eld properventclearancescanbemaintained Theheatshieldisnotincluded with the fireplace Toinstalltheheatshield slideonesectionovertheventpipeontheinsideofthewall opening withthecircularportioninsidethewallcavity Screwtheshieldinplaceover thewallopening Installthesecondsectionontheoutsideofthewallopeningsliding the circular portion into the wall opening Refer to Figure 16b Installation of Rear Vent T...

Page 13: ...s Fireplace Facing When selecting the finish material for your fireplace it is important to remember that THE OPENING MUST NOT BE OBSTRUCTED IN ANY WAY Doing so restricts the air supply for the control compartments and heat exchanger as well as prevents access for servicing controls The face of the fireplace may be painted to match the room decor provided you use aheat resistantpaint Decorativefac...

Page 14: ...ention to combustible materials New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot and energy efficient Please be aware that temperatures over the mantel will rise above normal room temperature and walls above fireplace may be hot to touch Figure 24a Threepiececombustibleframingshield Fasteners 3 ...

Page 15: ...gschematicforoptionalfans G L2 WH L1 BLK p g Quick Connect lu to motor 5 1 60 Supply G L1 L2 Removing and Installing the Door The doors are removed in a few simple steps Follow the steps below to remove the horizontal access panel unlatch the door buckles and remove the door Replace in reverse order Figure 28a Locatethedoorbuckles bothsidestypical Figure 28 Removingandinstallingthehorizontalaccess...

Page 16: ... spring tension Caution The latch springs back with force Hold the tool securely 4 Step7 Remove the tool from the latch slot Ensure the latches are hang ing freely and the hook end is released from the bottom of the door Repeat all four steps for the remaining latches Figure 28d Figure 28e Figure 28f Step8 Grasp the door on either side usually midway and lift the door carefully up andawayfromthefr...

Page 17: ...ip down the lower trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near thefloor Ifyouthensmellgas STOP Follow B inthesafetyinformation above on this label If you don t smell gas go to the next step 5 Locate pilot burner Seeillustrationatrig...

Page 18: ...ier s instructions If you cannot reach your gas supplier call the Fire Department C Use only your hand to push in or turn the gas control knob Never use 1 Turn off remote switch 2 Remove the lower horizontal access panel 3 Turn the incoming gas control valve to Off 4 Replace the lower horizontal access panel 1 STOP Read the safety information above on this label 2 Remove the lower horizontal acces...

Page 19: ...gure 32 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counter clockwise To lower the flame height turn clockwise Figure 32 Hi Lo AdjustmentontheDV52gasvalve Cleaning When the fireplace is first activated there may be some smoking and a visible film may be left on the glass This is a normal condition and is the result of burning of ...

Page 20: ...t screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check Figure33 wiring diagram Main burner will 1 Check wiring see Figure 33 not light 2 Check wall switch for proper connection All service and repairs should be performed by a qualified agency All spare parts optional parts and accessories are available from your lo...

Page 21: ...ied by The Company 2 The European Home Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompanysoleobli...

Page 22: ...t 1 8m minimuminCanada L clearancetonon mechanicalairsupplyinlettobuildingorthecombustionairinlet toanyotherappliance 16inches 41cm minimumforappliances 100000BTU H 30kW M clearancetomechanicalairsupplyinlet 6feet 1 8m minimum N clearanceabovepavedsidewalkorapaveddrivewaylocatedonpublicproperty 7 feet 2 1m minimum P clearanceunderveranda porch deck orbalcony 16inches 41cm minimum tonon combustible...

Page 23: ...line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GASVENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the i...

Page 24: ...EUROPEAN HOME a division of Europa Ja Inc 376 Washington St Suite 203 Malden MA 02148 tel 781 324 8383 fax 781 324 8384 www europeanhome com ...

Reviews: