15
COMBUSTION AIR SUPPLY
In addition to the air that moves through the firebox opening, combustion air
MUST
also be provided
to the base of the flame in the Vision Gas Fireplace using
either one of two
methods:
Method 1- When using a European Home Surround
With this method, a minimum twenty square inch opening is cut in the wall face as shown in Figure 5.
When an optional European Home surround is mounted, this combustion air opening is hidden and
air will flow through a cutout in the bottom of the surround.
This combustion air opening should be cut within the 3” by 30” dimensions shown in Figure 5. This 3”
x 30” area begins 1” below the bottom of the lower frame trim.
Figure 5
Combustion
Air Opening
3”
30”
1”