37
OBSERVED PROBLEM:
D.
No pilot flame and control contin-
ues to spark
E.
Pilot is lit and control continues
to spark. Valve shuts off after 10-30
seconds. Valve operates manually.
F.
Pilot is lit and sparking stops.
Valve shuts off after 10-60 seconds.
Valve does not operate manually.
G.
Three short beeps while the motor
turns.
H.
Pilot flame lights but there is no
main gas flow.
REMEDY:
4. Replace valve and thermocouple inter-
rupter.
5. Replace receiver and
reprogram code as above.
1. Replace receiver and
reprogram code as above.
1. Use a digital multimeter set in
the mV range and measure
the voltage between the spade
connector closest to the thermocouple
(-) and thermocouple tube (+) itself. The
reading should be 21-30 mV.
2. Replace thermocouple.
3. Confirm regulator pressure
and sizing. Replace if necessary.
4. Replace valve. Do not over-
tighten the thermocouple.
1. Replace batteries.
1. Turn manual override knob to
ON position (see figure 4).
2. Turn flame to high fire by
pressing up button on remote
control.
3. Confirm regulator pressure,
and sizing. Replace valve if
necessary.
4. Replace valve.
POSSIBLE CAUSE:
4. Over tightened thermocouple.
5. Receiver
1. Receiver
1. Not enough voltage generated
from the thermocouple or too much
resistance in the circuit.
2. Thermocouple
3. Low inlet pressure.
4. Valve
1. Batteries are low.
1. Manual override knob is in MAN
position.
2. Valve turned down to pilot flow.
3. Low inlet pressure.
4. Valve.