www.EUROPOWERgenerators.com
EP10000E-EP12000TE-IP54-EP13500TE-EP12000E-EP16000TE-
EP14000E-EP18000TE
Pg. 9 / 13
Doc.nr.:0004598
Opsteller: MH
Revisie:02
Revisor: BL
Opsteldatum: 15/04/2020
Goedkeurder: GD
Revisiedatum: 28/06/2021
5.3. Stopping the generating set:
-
let the generating set cool down at no load for a few minutes before
stopping the engine
-
stop the engine with the starting key
close the fuel cock.
CLOSE
5.4. Automatic Idle System (only for EP12000E, EP16000TE, EP14000E and
EP18000TE):
-
to switch on the A.I.S. system you have to turn the switch to the ON
position
-
the generating set will automatically turn to a reduced speed (2300
200rpm for GX690 and 2000 rpm for iGX800) when there is no load
connected, or when the load has been removed. When a minimum load
(100 to 200W) is connected it will return to its nominal speed
(3000rpm).
Note:
-
it can happen that the A.I.S. function does not react on some small
(electronic) charges. When this occurs, turn off the A.I.S. system by
turning the switch to OFF position
-
“OFF DELAY” is set at 60 sec (
-25% + 50%).: this means that the
engine will automatically turn to a reduced speed +/- 60 sec after
switching off the charge. This is to prevent excessive ON/OFF
switching of the engine.
-
the
“OFF DELAY”
-regulator is sealed. It is forbidden to change this
setting.
5.5. Cooling
-
make sure that there are no obstructions at the fresh air intake
grid, which provides cooling air for the engine and the
alternator.
-
make sure that the hot cooling air from the engine and the
alternator, as well as the exhaust gasses, can easily be abducted.
-
never let the generator run in an inappropriately ventilated room!
(danger of CO poisoning)
5.6. Protections:
-
engine: low oil level protection
-
alternator: thermal-magnetic protection.