EUROSTER 1100Z – USER MANUAL

3

d. DHW priority

for switching the DHW priority on/off simultaneously press the two switches under the 
display until the right outermost dot on the LED display changes its status. The DHW 

priority is on when the light comes up, and off - when the light is off.

e. cylinder cooling protection

the function is active by default and indicated by continuous (not blinking) display at 
controller start up. 

for   deactivating   the   cooling   protection   press   either   of   the   presetting  switches   while 
powering up the controller with the mains switch (~). Deactivation of the function is 

indicated by blinking of display (figures 88) two times before displaying the current 
temperature.

for activating the cooling protection repeat the above described procedure.

f. setting the temperatures 

setting the temperature for the DHW circulating pump: press the left-hand switch under 
the display – the figures will start blinking indicating that the current DHW temperature 

setpoint is being displayed,

use   the   right-hand   or   left-hand   switches   to   increase/   decrease   the   displayed 
temperature setpoint, as appropriate,

after ca. 4 sec. the display will stop blinking indicating that the preset temperature has 
been stored. The display will return to displaying the current temperature, as measured 
by the sensor on the heating circuit. 

setting the temperature for the heating water circulating pump: press the right-hand 
switch under the display – the figures will start blinking indicating that the current DHW 

temperature setpoint is being displayed,

use   the   right-hand   or   left-hand   switches   to   increase/   decrease   the   displayed 
temperature setpoint, as appropriate,

after ca. 4 sec. the display will stop blinking indicating that the preset temperature has 
been stored. The display will return to displaying the current temperature, as measured 
by the sensor on the heating circuit. 

g. automatic operation mode

set the right hand switch (

) to 0

Cooling protection on:

the DHW pump is operated as follows: the pump is switched on when the temperature 
measured by the DHW sensor has dropped below the setpoint and the heating water 
temperature is higher by 6°C than the cylinder temperature, as a protection against 

excessive cooling. With active cylinder cooling protection the controller will switch off 
the heating water circulating  pump. The DHW  circulating pump  will be switched  off 

when the temperature on the hot water cylinder has risen 1°C above the setpoint or the 
temperature difference between the boiler and the DHW cylinder has reached 4°C. The 

pump will be restarted when the temperature on the DHW cylinder has dropped by 2°C 
below the setpoint.

the heating water circulating pump is operated as follows: the pump is switched on 
when the temperature measured by the heating water sensor has risen by 2°C above 

the setpoint and it is switched off when the temperature has dropped by 3°C below the 
setpoint. With active DHW priority the heating water circulating pump will be switched 

on only when the DHW pump is off. 

Cooling protection off:

heating of water in the cylinder is governed solely by the temperature measured by the 
DHW sensor. The pump is switched on when the temperature has dropped below the 

setpoint and switched off when it has risen by 1°C above that setting. The operation of 
the  heating water  pump is the same  as described for  operation  with  active  cooling 

protection.