background image

EUROSTER 11K CONTROLLER USER MANUAL

6

controller/its sensor fails or in case of a power supply black out. 

f) Detection of sensor failures and other dangerous situations

Following events are recognized by the controller:

Event

On screen 

Pumps

AUX output

Acoustic signal

Sensor open
Deep freeze 

OP

on

on

no

Freezing

LO

off

in line with the

control algorithm 

no

Critical temperature exceeded

Temperature

on

off

no

Alarm temperature exceeded

Temperature

on

off

yes

Overheating

Hi

on

off

yes

Sensor short-circuited

Strong overheating 

SH

on

on

yes

Each of the above events:

cancels ignition function (if activated)

starts to blink controller screen contents.

In case of a single error of the S1/S2 sensor, the 

/

 light is lit, respectively. In case of

more than one simultaneous errors, only the highest priority error is signaled. Error priorities:

S1 sensor failed (

SH

 or 

OP

)

S2 sensor failed (

SH

 or 

OP

)

S1 sensor overheated or frozen (

LO

 or 

Hi

)

S2 sensor overheated or frozen (

LO

 or 

Hi

)

S1 sensor temperature too high 

S2 sensor temperature too high.

g) Alarm output (optional)

In case of an alarm all pump outputs (including outputs not used in the given system layout)
are activated. It means that each unused pump output may be used as an alarm signal.

The 

P3

 output is equipped with both normally open (NO) and normally closed (NC) contacts.

In case of an alarm, mains voltage normally connected to the NC contact is switched over to

the NO contact.

h) Acoustic alarm 

Should  the   fireplace   water   jacket/CH   tank   temperature   exceed   the   alarm   threshold,   an
acoustic alarm signal is activated. Press any button to stop the signal for 5 minutes.

i) The ANTY-STOP function

The 

ANTY-STOP

 function turns the CH system pump(s) on every 14 days for 30 s (to prevent

rotor seizing). "AS" letters are blinking on the controller display while the function is active. 

j) DWH priority

In CH systems with DWH tanks the DWH function may be assigned a higher priority than the
CH function. If this is the case, the controller will turn the CH system off should heating of

DHW   be   needed   (to   shorten   time   necessary  to   heat   the   DHW   tank   up).   A  modified   DHW
priority function implemented in E11K controllers prevents room temperature to drop down too

much while the DHW tank is heated: every now and then (preset period) the function is turned
off for 10 minutes so that the CH pump may be turned on for that time.

The DHW function period may be set as the 

Pr

 installer parameter value. For example if 

Pr 

=

30, the DWH priority function will be suspended and the CH pump turned on every 30 minutes

(for 10 minutes). The 

Pr

 = 0 value disables the DWH priority function, which means that the

CH pump will operate regardless of the DHW tank temperature.

Summary of Contents for 11K

Page 1: ...he controller may control systems built according to one of the three following layouts CH system with a plate heat exchanger CH system with a heat buffer CH system with a plate heat exchanger and a DWH tank In all layouts the controller adjusts the combustion processes by opening closing the fireplace throttle depending on the measured temperatures and information received from the cooperating ro...

Page 2: ... the controller off 2 decrement the displayed value turn the ignition off 3 increment the displayed value turn the ignition on 4 accept the displayed value turn the controller on enter the setup mode 3 INSTALLATION ATTENTION Hazardous voltages may be present inside the controller and on its cables Therefore it is expressly forbidden to install the device unless its mains power supply is disconnect...

Page 3: ...e the controller power supply cord must be unplugged before any works are started The procedure a Mount the S1 sensor do not immerse the sensor into any liquid nor install it within chimney flue gas stream install sensor at some external surface of the fireplace water jacket or on an uncovered segment of the fireplace outlet pipe as close to the fireplace as possible using a hose clip tighten the ...

Page 4: ...actuated by a 230 VAC actuator In absence of power the throttle should close automatically connect protective wires of the pumps and of the throttle with the PE power cord wire ATTENTION Controller is a 2nd insulation class device so it needs no grounding However every cooperating device that needs to be grounded must be obligatorily connected to the protective wire f Hook up power supply cable co...

Page 5: ... that not happen within 1 hour the controller will cancel the ignition function and close the throttle Otherwise it will resume normal operation Activation of the ignition function is signaled by the light The function is activated automatically once the controller is turned on It may also be activated manually using the button Press the button to deactivate the ignition function e Cooperation wit...

Page 6: ...output is equipped with both normally open NO and normally closed NC contacts In case of an alarm mains voltage normally connected to the NC contact is switched over to the NO contact h Acoustic alarm Should the fireplace water jacket CH tank temperature exceed the alarm threshold an acoustic alarm signal is activated Press any button to stop the signal for 5 minutes i The ANTY STOP function The A...

Page 7: ...ayouts 2 and 3 THROTTLE Preset fireplace temperature throttle activation threshold Range 20 or tb 70 or OH 5 C Standard value 55 C AUX Temperature at which the AUX output is deactivated Range 20 85 C Standard value 35 C b Installer parameters service mode settings ATTENTION Installer parameters must be modified knowledgeably or else the CH system may start to work incorrectly Therefore the paramet...

Page 8: ...eds the tE threshold OF Automatic shut down delay Range 0 30 min Standard value 5 min The controller will shut down automatically OF minutes after the time when the fireplace temperature has dropped down below the tE threshold OF 0 the controller will never shut down automatically C1 S1 sensor offset Range 5 5 C Standard value 0 C That parameter may be used to correct temperature readings C2 S2 se...

Page 9: ...d with a delay in respect to P1 activation time if the fireplace temperature exceeds the preset temperature P3 alarm output is activated if the fireplace temperature exceeds the critical temperature AUX output is deactivated if the fireplace temperature exceeds the AUX temperature or RT is turned off Throttle is controlled open closed to maintain the preset temperature b Layout 2 CH system with he...

Page 10: ...ICATES The E11K controller meets all requirements of the EMC and the LVD EU Directives The CE Conformity Declaration is available on the http www euroster com pl Internet webpage 8 SPECIFICATIONS a Temperature range 0 C 99 C b Mains 230 V 50 Hz c Combined current consumption max 3 A d Case flush fitting 4M electrical box 4 KIT CONTENTS a Euroster 11K controller b S1 temperature sensor with 2 m lon...

Page 11: ... may be repaired exclusively by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs by unauthorized persons 6 This consumer warranty does not exclude restrict nor suspend any right of the Buyer ensuing if the product would not meet any of the sale contract terms sale ...

Reviews: