background image

BA_S011 
Operation Manual 

EUROTEC Antriebszubehör GmbH | Bildstock 37 | DE-88085 Langenargen | sales@eurotec-shop.com | www.eurotec-shop.com | 19.11.2015 | Seite 5 von 5

 

 

 

 

 

 

 

Fig. 9: -MA 

Fig. 10: -2MA 

Fig. 11: -2KV 

Fig. 11: -2NPT1/2 

Fig. 12: -MA12 

11.

 

Outdoor use 

If you like to use the limit switch boxes for an outdoor application, you will need a venting element. This venting element will help to avoid 
condensation water inside the switch box housing due to ambient temperature variations. Please verify if a venting element is present at 
your limit switch box. Otherwise you need to order a suitable limit switch box with venting element. The order code “-DAE” needs to be 
added to the actual part number. 

12.

 

Maintenance 

With the long-term outdoor use of the switch boxes and with extremely high or low ambient temperatures, the cover and shaft sealings can 
become porous. A safe use can only be guaranteed with a leak-proof housing. Sealings need to be replaced as soon as they are worn out, 
but no later than after 5 years. The necessary sealings can be ordered from EUROTEC. 

13.

 

Malfunctions 

If a malfunction occurs, check the electric line connections, the supply voltage, the cam position, condensation water inside the housing, the 
proper function of the pneumatic actuator and of the valve below the actuator. Rectify any possible faults. If this does not rectify the 
malfunction, be sure the there is no pressure on the device and disconnect the device from the power supply voltage. Consult an authorised 
and trained specialist member of the manufacturer’s staff. 

14.

 

Part number 

 

Reviews: