)XQFWLRQ
#
%ORFNV
##
8096
953#
9HFWRU
#
'ULYH
#0#
+$
7968;7
127(6
=
The Value of PERSISTENT DATA::COUNT should be monitored to check that it is approximately equal to the
number of power downs. The Eeprom is only rated for 10000 writes.
The Persistent data is not saved in the same area as the parameter data, any error in the data’s integrity will be
flagged at power up. Pressing the ‘E’ key acknowledges the fault.
If this happens the drive reverts to the last saved value on the tags.
If the tag numbers of the persistent data area are different the data is also lost. This may happen if you change the tag
list.
6<67(0
#2
&21),*85(
#
,
2
2
&21),*85(
#
(1$%/(
During the process of reconfiguration there is a danger that Tag numbers will be connected to wrong parameters. To
avoid this possibility all configuration links must be temporarily "disconnected" during the configuration process and
the flag set to "enabled" to allow the activity. Failure to reset the flag to "disabled" after reconfiguration will cause
an alarm to be generated, "Configure Enabled", which will prevent drive operation.
$1$/2*8(
#
,13876
00,
#
(175,(6
f.......ANALOG INPUTS
f.........ANIN 1 (C3)
f...........CALIBRATION [248] = 100.00 %
f...........OFFSET [358] = 0.00 %
f...........MAX VALUE [249] = 100.00 %
f...........MIN VALUE [250] = -100.00 %
f...........DESTINATION TAG [251] = 196
f...........SCALED INPUT [390] = 0.00 %
f...........ANIN 1 (C3) [29] = 0.000 VOLTS
f.........ANIN 3 (F2)
f...........CALIBRATION [256] = 100.00 %
f...........OFFSET [360] = 0.00 %
f...........MAX VALUE [257] = 100.00 %
f...........MIN VALUE [258] = -100.00 %
f...........DESTINATION TAG [259] = 197
f...........SCALED INPUT [391] = 0.00 %
f...........ANIN 3 (F2) [31] = 0.000 VOLTS
f.........ANIN 4 (F3)
f...........CALIBRATION [261] = 100.00 %
f...........OFFSET [361] = 0.00 %
f...........MAX VALUE [262] = 100.00 %
f...........MIN VALUE [263] = -100.00 %
f...........DESTINATION TAG [264] = 0
f...........SCALED INPUT [392] = 0.00 %
f...........ANIN 4 (F3) [32] = 0.000 VOLTS
f.........ANIN 5 (F4)
f...........CALIBRATION [266] = 100.00 %
f...........OFFSET [362] = 0.00 %
f...........MAX VALUE [267] = 100.00 %
f...........MIN VALUE [268] = -100.00 %
f...........DESTINATION TAG [269] = 0
f...........SCALED INPUT [393] = 0.00 %
f...........ANIN 5 (F4) [33] = 0.000 VOLTS
h.........ANIN FILTER [671] = 0.800
This manual was downloaded on www.sdsdrives.com