3200 Series
100 Part No HA028651 Issue 7.0 Apr-09
16.4
Calibration Parameters
The following table gives the parameters available in the Calibration List.
The User Calibration is available in Level 3 only and is used to calibrate ‘Offset’ see section 8.2.
CALIBRATION PARAMETER LIST
‘
cAL
’
Name
Scrolling
Display
Parameter
Description
Value
Default
Access Level
IdLe
Normal operating state
Lo
Low offset
Hi
High offset
u c a l
USER
CALIBRATION
To select low and high
offset state or reset to
no offsets. See section
16.2.2.
rEST
Remove high and low offsets
IdLE
L3 only
The following parameters appear when calibrating the controller ie UCAL = Lo or Hi
c . a d j
CALIBRATION
ADJUST
To set an offset value.
See section 16.2.2.
-1999 to 9999
L3 only
Input and Output calibration can only be done in
Conf
level.
CALIBRATION PARAMETER LIST
‘
cAL
’
Name
Scrolling
Display
Parameter
Description
Value
Default
Access
Level
none
Not selected
0
Select mV low calibration point
50
Select mV high calibration point
150r
Select PRT low cal point
400r
Select PRT high cal point
CJC
Select CJC calibration
Ct 0
Select CT low cal point
Ct 70
Select CT high cal point
Fact
Return to factory settings
Ima.L
Low mA output from I/O 1
Ima.H
High mA output from I/O 1
2ma.L
Low mA output from output 2
2ma.H
High mA output from output 2
3ma.L
Low mA output from output 3
3ma.H
High mA output from output 3
rm.VL
Remote setpoint input low volts
rm.VH
Remote setpoint input high volts
rm.CL
Remote setpoint input low current
p h a s e
CAL PHASE
To calibrate low and
high offset
rm.CH
Remote setpoint input high current
none
Conf only
NO
Yes
Start
Busy
Calibrating
Pass
Calibration successful
G O
To start the calibration
sequence
faiL
Calibration unsuccessful
NO
Conf only