3200 Series
Part No HA028651 Issue 7.0 Apr-09 29
5.8.3
To Configure the Programmer
Select Access Level 2 – see section 5.
Operation
Action
Indication
Notes
Configure
the Timer as
a
Programmer
1.
Press
°
to select
‘TM.CFG’
2.
Press
W
or
V
to ‘
ProG
’
Set the
Resolution
3.
Press
°
to select
‘TM.RES’
4.
Press
W
or
V
to ‘
Hour
or
‘
min
’
’
In this example the ramp rate and
dwell period are set in hours
Set the
Threshold
5.
Press
°
to select
‘THRES’
6.
Press
W
or
V
to adjust
In this example the dwell periods will
not start until the PV is within 5 units
of the setpoint
Set the
action when
the
programmer
times out
7.
Press
°
to select
‘END.T’
8.
Press
W
or
V
to ‘
Off
’ or
‘
SP2
‘ or ‘
Dwel
’ or ‘
rst
’
In this example the controller will
continue to control indefinitely at the
last setpoint.
OFF will turn the output power.
SP2 will control at setpoint 2
Reset will control at the selected
setpoint
Set the
Servo Mode
9.
Press
°
to select ‘SERVO’
10.
Press
W
or
V
to ‘
PV
’, ‘
SP
‘,
‘
SP.rb
’, or ‘
PV.rb
’
In this example the program will start
from the current value of the process
temperature. See also section 5.8.1.
Set the first
Target
Setpoint
11.
Press
°
to
select ‘TSP.1’
12.
Press
W
or
V
to adjust
In this example the setpoint will ramp
from the current value of the PV to
the first target - 100
Set the first
Ramp Rate
13.
Press
°
to select
‘RMP.1’
14.
Press
W
or
V
to adjust
In this example the setpoint will ramp
to 100 at 8.0 units per hour
Set the first
Dwell
15.
Press
°
to select
‘DWEL.1’
16.
Press
W
or
V
to adjust
In this example the setpoint will
remain at the start value for 2 hours
11 minutes
Repeat the above three steps for all segments
Notes:-
•
It is possible to set, in a deeper level of access, Event Outputs and Programmer Cycles. See sections 13.2.3 and 13.2.4.
•
‘Event Outputs’ is available in software version 2 and above. A digital event may be configured to operate in any
segment of the program. This event may be configured to operate a digital output.
•
‘Programmer Cycles’ is available from software versions 2.09 (PID controllers) and 2.29 (Valve Position controllers).
This allows the programmer to repeat the set program up to 100 times.