3200 Series
38 Part No HA028651 Issue 7.0 Apr-09
INPUT LIST
I N P U T
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
m v . i n
MILLIVOLT
INPUT VALUE
Millivolts measured at the rear
PV Input terminals
xx.xx mV - read only
Conf
L3 R/O
R c . f t
ROC FILTER TIME
This provides a first order filter
for the rate of change filtering
function and can be used to
avoid nuisance alarm triggers due
to short duration noise on the
calculated rate of change,
oFF
to
0.1
to
999.9
minutes
Off means no filtering applied
1.6
L3
R C . P V
PV DERIVATIVE
Provides a measure of the
calculated rate of change of the
temperature or measurement
input as used by the Rate of
Change Alarm functions. Useful
when commissioning to
determine the level of filtering
required on the Rate of Change
alarm.
L3
8.1.1
Input Types and Ranges
Input Type
Min Range
Max Range
Units
Min Range
Max Range
Units
J.tc
Thermocouple type J
-210
1200
o
C -346 2192
o
F
k.tc
Thermocouple type K
-200
1372
o
C -328 2502
o
F
L.tc
Thermocouple type L
-200
900
o
C -328 1652
o
F
r.tc
Thermocouple type R
-50
1700
o
C -58
3092
o
F
b.tc
Thermocouple type B
0
1820
o
C 32
3308
o
F
n.tc
Thermocouple type N
-200
1300
o
C -328 2372
o
F
t.tc
Thermocouple type T
-200
400
o
C -328 752
o
F
S.tc
Thermocouple type S
-50
1768
o
C -58
3215
o
F
Rtd
Pt100 resistance thermometer
-200
850
o
C -328 1562
o
F
mv
mV or mA linear input
-10.00
80.00
Cms
Value received over digital
communications (modbus
address 203).
This value must be updated every
5 seconds or the controller will
show sensor break