3200 Series
Part No HA028651 Issue 7.0 Apr-09 43
INPUT/OUTPUT LIST 1 ‘
I O -1
’
Name
Scrolling Display
Parameter Description
Value
Default
Access Level
1 . P L S
OUTPUT 1
MINIMUM PULSE
TIME
Minimum output on/off
time.
Only applies to time
proportioning outputs and
prevents relays from
switching too rapidly
0.0
to
150.0
Auto or 1.0 to 150.0 seconds
Auto = 110mS
5.0 sec
for
relay.
Auto
for
logic
Conf
1.SENS
I/O 1 SENSE
To configure the sense of
the input or output
channel
See also section 9.1.3
nor
Inv
Normal
Inverted
nor
Conf
0.20
0-20mA output
1 . r n g
DC OUTPUT
RANGE
To configure 0-20mA or 4-
20mA output
Only appears if the output
module is DC output
4.20
4-20mA output
L3
Note 1:-
A DC output may require calibration. This is described in section 16.3.4.