3200 Series
Part No HA028651 Issue 7.0 Apr-09 51
10.2
Example: To Set Ramp Rate
This is available in Level 3.
Do This
The Display You
Should See
Additional Notes
1.
Press
as many times as necessary
to select
‘SETPOINT LIST’
2.
Press
°
as many times as necessary
to scroll to ‘SP1’
3.
Press
V
or
W
to adjust setpoint 1
This step can be repeated for the lower setpoint limit
‘
SP.LO
’
4.
Press
°
to scroll to ‘SP2’
5.
Press
V
or
W
to adjust setpoint 2
6.
Press
°
as many times as necessary
to scroll to ‘SP.RAT’
7.
Press
V
or
W
to set the rate at
which you require the setpoint to
change
Whenever the setpoint is changed, the controller will
ramp from its current setpoint to the new value at the
rate set in units per second, minute or hours as set by
the ‘RAMPU’ parameter.
It will also change at the same rate when switching
between SP2 and SP1 (but not between SP1 and SP2)
The setpoint rate resolution is generally one decimal
point more than setpoint/PV resolution
73.00
s p 1
50.00
s p 2
6.000
S p . r a t