3200 Series
64 Part No HA028651 Issue 7.0 Apr-09
12.3
Alarm Parameters
Four alarms are available. Parameters do not appear if the Alarm Type = None. The following table shows the
parameters to set up and configure alarms.
ALARM LIST
‘
ALARM
’
Name
Scrolling Display
Parameter Description
Value
Default
Access
Level
none
Alarm not configured
Hi
Full Scale High
Lo
Full Scale Low
d.Hi
Deviation High
d.Lo
Deviation Low
bnd
Deviation band
rrc
Rising rate of change,
set in 1-9999 eng
units/min
A1.TYP
ALARM 1 TYPE
Selects the type of alarm
Frc
Falling rate of change
set in 1-9999 eng
units/min
As order
code
Conf
A 1 . - - -
ALARM 1
SETPOINT
Alarm 1 threshold value.
The last three characters show the
type of alarm configured from the
above list
Instrument range
0
L3
OFF
Alarm off
A 1 . s t s
ALARM 1 OUTPUT
Indicates the status of the alarm
On
Alarm on
Read only
A1.HYS
ALARM 1
HYSTERESIS
See description at the beginning of
this section
0 to 9999
Conf
none
Non-latching
Auto
Latching with
automatic resetting
Man
Latching with manual
resetting
A1.LAT
ALARM 1
LATCHING TYPE
See description at the beginning of
this section
Evt
Event (no alarm
flashing beacon but
messages can be
displayed)
As order
code
Conf
No
No blocking
A1.BLK
ALARM 1
BLOCKING
See description at the beginning of
this section
yes
Blocking
No
Conf
The above parameters are repeated for Alarm 2,
A2
; Alarm 3,
A3
; Alarm 4,
A4