3200 Series
66 Part No HA028651 Issue 7.0 Apr-09
12.4
Diagnostic Alarms
Diagnostic alarms indicate a possible fault within the controller or connected devices.
Display shows
What it means
What to do about it
E.Conf
A change made to a parameter takes a finite time to
be entered. If the power to the controller is turned
off before the change has been entered then this
alarm will occur.
Do not turn the power off to the controller while
ConF
is flashing
Enter configuration mode then return to the
required operating mode. It may be necessary to re-
enter the parameter change since it will not have
been entered in the previous configuration.
E.CaL
Calibration error
Re-instate Factory calibration
E2.Er
EEPROM error
Return to factory for repair
EE.Er
Non-vol memory error
Note the error and contact your supplier
E.Lin
Invalid input type. This refers to custom
linearisation which may not have been applied
correctly or may have been corrupted.
Go to the INPUT list in configuration level and set a
valid thermocouple or input type
Emod
IO1, OP2, or OP3 has been changed
If this has been field changed by the installation of a
new board, enter config level, then exit back to
operator level.
If the message occurs at any other time return to
factory for repair.
12.4.1
Out of Range Indication
If the input is too high HHHHH will be displayed
If the input is too low LLLLL will be displayed