3200 Series
68 Part No HA028651 Issue 7.0 Apr-09
TIMER LIST
‘
t i m e r
’’
Name
Scrolling
Display
Parameter Description
Value
Default
Access
Level
sp.rb
Starts at SP1 (or SP2).
The program will continue to run
from the original setpoint value
at the last ramp rate.
pv.rb
Starts at the current Process
value.
The program will continue to run
from the current process value
and ramp back at the last ramp
rate
T s p . 1
TARGET SETPOINT
1
To set the target value for
the first setpoint
Controller input range
0
L2
R m p . 1
RAMP RATE 1
To set the rate at which the
setpoint changes to reach
TSP.1
Off
, 0:1 to 3000 units per min or hour
Off
L2
D w e l . 1
DWELL 1
To set the time at which the
setpoint remains at TSP.1
Off
, 0:01 to 99:59 hh:mm or mm.ss
Off
L2
The above three parameters are repeated for the next 3 program segments, i.e. TSP.2, (3 & 4), RMP.2 (3 & 4), DWEL.2 (3 & 4)
d w e l l
SET TIMER
DURATION
To set the time duration
(not
programmer)
0:00 to 99:59 hh:mm or mm.ss
0
L3
T . E L A P
ELAPSED TIME
Time elapsed from when the
timer starts to run
0:00 to 99.59 hh:mm or mm.ss
L3 read
only
T . R E M N
TIME
REMAINING
Time remaining to reach the
set time.
0:00 to 99.59 hh:mm or mm.ss
L3
e v e n t
EVENT OUTPUTS
Event output operates during the
selected segment
Programmer only
See section 13.2.3
0 = No events operate in any segment
255 -= Events operate in all segments
0 L3
p . c y c l
PROGRAM
CYCLES
Sets the number of times that a
program is repeated
1 to 100
1
L3
c y c l e
PROGRAM CYCLE Displays the current cycle when the
program is running
1 to 100
L3
The timer can be restarted from the Reset condition by changing the time remaining parameter.