3200 Series
86 Part No HA028651 Issue 7.0 Apr-09
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
2 – Latching Sensor Break
Id
Customer ID – May be set to any value between 0-9999 for identification of instruments in applications. Not used
by the instrument itself.
629
PHASE
Calibration Phase
0 – None
1 – 0 mv
2 – 50 mv
3 – 150 Ohm
4 – 400 Ohm
5 – CJC
6 – CT 0 mA
7 – CT 70 mA
8 – Factory Defaults
9 – Output 1 mA low cal
10 – Output 1 mA high cal
11 – Output 2 mA low cal
12 – Output 2 mA high cal
13 – Output 3 ma low cal (3208/3204 only)
14 – Output 3 ma high cal (3208/3204 only)
15 – Remote setpoint input low volts
16 - Remote setpoint input high volts
17 - Remote setpoint input low current
18 - Remote setpoint input high current
768
GO
Calibration Start
0 – No
1 – Yes (start cal)
2 – Cal Busy
3 – Cal Pass
4 – Cal Fail
Note values 2-4 cannot be written but are status returns only
769
-
Analogue Output Calibration Value
775
K.LOC
Allows instrument to be locked via a key/digital input
0 - unlocked,
1 – all keys locked
2 – Edit keys (raise and lower) disabled
3 – Mode key disabled
4 – Manual mode disabled
5 – Enter standby mode when Mode combination pressed
6 – Timer keys disabled
1104
Dwel.1
Programmer Dwell 1 Duration
1280
TSP.1
Programmer Target Setpoint 1
1281
RMP.1
Programmer Ramp Rate 1
1282
Dwel.2
Programmer Dwell 2 Duration
1283
TSP.2
Programmer Target Setpoint 2
1284
RMP.2
Programmer Ramp Rate 2
1285
Dwel.3
Programmer Dwell 3 Duration
1286
TSP.3
Programmer Target Setpoint 3
1287
RMP.3
Programmer Ramp Rate 3
1288
Dwel.4
Programmer Dwell 4 Duration
1289
TSP.4
Programmer Target Setpoint 4
1290
RMP.4
Programmer Ramp Rate 4
1291
AT.R2G
Auto-tune Configures R2G
0 - YES
1 - No
4176
IN.TYP
Input Sensor Type
0 – J Type Thermocouple
1 – K Type Thermocouple
2 – L Type Thermocouple
12290