3200 Series
Part No HA028651 Issue 7.0 Apr-09 89
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission
1.RNG
IO Channel 1 DC Output Range
0 – 0-20mA
1 – 4-20mA
12676
1.SRC.A
IO Channel 1 Source A
0 – None
1 – Alarm 1
2 – Alarm 2
3 – Alarm 3
4 – Alarm 4
5 – All Alarms (1-4)
6 – New Alarm
7 – CT Alarm (Load, Leak or Overcurrent)
8 – Loop Break Alarm
9 – Sensor Break Alarm
10 – Timer End (or Not Ramping)
11 – Timer Run (or Ramping)
12 – Auto/Manual
13 – Remote fail
14 – Power fail
15 – Programmer event
12678
1.SRC.B
IO Channel 1 Source B
As IO Channel 1 Source A (Modbus address 12678)
12679
1.SRC.C
IO Channel 1 Source C
As IO Channel 1 Source A (Modbus address 12678)
12680
1.SRC.D
IO Channel 1 Source D
As IO Channel 1 Source A (Modbus address 12678)
12681
1.SENS
Configures the polarity of the input or output channel (0 = Normal, 1 = Inverted)
12682
1.PLS
IO1 Time proportioning Output minimum pulse time
12706
2.ID
Output 2 Type
0 – None
1 – Relay
2 – Logic Output
3 – DC OP
4 – Triac (SSR)
12736
2.FUNC
Output 2 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
2 – Heat or UP if valve position
3 – Cool or DOWN if valve position
10 – DC Output no function
11 – DC Output Heat
12 – DC Output Cool
13 – DC Output WSP retransmission
14 – DC Output PV retransmission
15 – DC Output OP retransmission
12739
2.RNG
IO Channel 2 DC Output Range
0 – 0-20mA
1 – 4-20mA
12740
2.SRC.A
Output 2 source A
As IO Channel 1 Source A (Modbus address 12678)
12742
2.SRC.B
Output 2 source B
As IO Channel 1 Source A (Modbus address 12678)
12743
2.SRC.C
Output 2 source C
12744