14 Part number HA028582. Issue 6.0 May-07
2.6
Input/Output 1 & Output 2
May be configured as input or output.
Outputs can be logic (SSR drive), or relay, or mA dc.
Input is contact closure.
Relay Output
(Form A, normally open)
•
Isolated output 240Vac CATII
•
Contact rating: 2A 264Vac resistive
•
Output functions: Heating, or cooling,
or alarm or motorised valve open or
closed
Logic (SSR drive) Output
•
Not isolated from the sensor input
•
Output ON state: 12Vdc at 40mA
max
•
Output OFF state: <300mV,
<100
μ
A
•
Output functions: Heating, or
cooling, or alarm or motorised
valve open or closed
•
The output switching rate must be set to prevent
damage to the output device in use. See
parameter 1.PLS or 2.PLS in section 5.3
DC Output
•
Not isolated from the sensor input
•
Software configurable: 0-20mA or 4-
20mA.
•
Max load resistance: 500
Ω
•
Calibration accuracy: +(<1% of
r <100
μ
A)
•
Output functions: Heating, or cooling, or
retransmission.
Triac Output
•
Isolated output 240Vac CATII
Rating: 0.75A rms, 30 to 264Vac
resistive
Logic Contact Closure Input (OP1 only)
•
Not isolated from the sensor input
•
Switching: 12Vdc at 40mA max
•
Contact open > 500
Ω
. Contact closed
< 150
Ω
•
Input functions: Please refer to the list
in the Quick Start codes.
OP1/2
1(2) A
1(2)B
OP1
1A
1B
+
-
OP1/2
1(2) A
1(2)B
+
-
OP1/2
1(2) A
1(2)B
1(2) A
1(2)B
Summary of Contents for 3200
Page 1: ...3200PID Temperature controllers User Guide Manuel Utilisateur Bedienungsanleitung ENG FRA GER ...
Page 57: ...3200Régulateurs de température PID Manuel Utilisateur FRA ...
Page 58: ......
Page 116: ...58 3200 Guide utilisateur HA028582FRA Indice 6 0 mai 07 ...
Page 117: ...3200PID Temperaturregler Bedienungsanleitung GER ...
Page 118: ......
Page 173: ......