26 Part number HA028582. Issue 6.0 May-07
•
For general guidance refer to Eurotherm Controls
EMC Installation Guide, HA025464.
•
When using relay outputs it may be necessary to fit
a filter suitable for suppressing the emissions. The
filter requirements will depend on the type of load.
For typical applications we recommend Schaffner
FN321 or FN612.
•
If the unit is used in table top equipment which is
plugged into a standard power socket, then it is
likely that compliance to the commercial and light
industrial emissions standard is required. In this
case to meet the conducted emissions requirement, a
suitable mains filter should be installed. We
recommend Schaffner types FN321 and FN612.
Routing of wires
To minimise the pick-up of electrical noise, the low
voltage DC connections and the sensor input wiring
should be routed away from high-current power
cables. Where it is impractical to do this, use shielded
cables with the shield grounded at both ends. In
general keep cable lengths to a minimum.