36 Part number HA028582. Issue 6.0 May-07
Mnemonic
Scrolling Display and description
Range
WKG.SP
WORKING SETPOINT
is the active setpoint value. It appears when
the controller is in Manual mode. It may come from SP1 or SP2, or, if
the controller is ramping (see SP.RAT), it is the present ramp value.
Read only value
SP.HI to SP.LO
WRK.OP
WORKING OUTPUT
is the output from the controller. It appears
when the controller is in Auto mode. In a motorised valve controller
(option VC or VP) this is the ‘inferred’ position of the valve
For On/Off control: OFF = <1%. ON = >1%
Read only value
0 to 100% for heating
0 to –100% for cooling.
Alterable value
rES
Reset
run
Running
hoLd
In hold
T.STAT
TIMER STATUS
is the current state of the timer: Run, Hold, Reset or
End
It is only appears when a timer is configured.
End
Timed out
O
C
o
C
O
F
o
F
O
k
Kelvin
nonE
o
C (beacon off)
UNITS
DISPLAY UNITS
Temperature display units. The percentage units
is provided for linear inputs
PErc
Percentage
SP.HI
SETPOINT HIGH
High setpoint limit applied to SP1 and SP2.
SP.LO
SETPOINT LOW
Low setpoint limit applied to SP1 and SP2
Alterable between range
limits
By default the remote setpoint is scaled between SP.HI and SP.LO. Two further parameters (REM.HI and
REM.LO) are available in a deeper level of access to limit the Remote SP range if required. See
Engineering Handbook HA027986 which can be downloaded from www.eurotherm.co.uk.
Summary of Contents for 3200
Page 1: ...3200PID Temperature controllers User Guide Manuel Utilisateur Bedienungsanleitung ENG FRA GER ...
Page 57: ...3200Régulateurs de température PID Manuel Utilisateur FRA ...
Page 58: ......
Page 116: ...58 3200 Guide utilisateur HA028582FRA Indice 6 0 mai 07 ...
Page 117: ...3200PID Temperaturregler Bedienungsanleitung GER ...
Page 118: ......
Page 173: ......