38 Part number HA028582. Issue 6.0 May-07
Mnemonic
Scrolling Display and description
Range
OFF
Control OP goes
to zero
Dwel
Control continues
at SP1
SP2
Go to SP2
END.T
TIMER END TYPE
This determines the behaviour of the timer when it
has timed out. This value can be changed while the timer is running.
res
Reset
programmer
SS.PWR
SOFT START POWER LIMIT
This parameter only appears if the timer
configuration is set to
sfst
(Softstart). It sets a power limit which is
applied until the measured temperature reaches a threshold value
(SS.SP)
or the set time
(DWELL)
has elapsed. The timer starts
automatically on power up.
-100 to 100%
SS.SP
SOFT START SETPOINT
This parameter only appears if the timer
configuration is set to
sfst
(Softstart). It sets the threshold value
below which the power is limited
Between SP.HI and SP.LO
DWELL
SET TIME DURATION
– Sets the dwell timing period. It can be
adjusted while the timer is running.
0:00 to 99.59 hh:mm: or
mm:ss
T.REMN
TIME REMAINING
Timer time remaining. This value can be increased
or decreased while the timer is running
0:00 to 99.59 hh:mm: or
mm:ss