Part number HA028582. Issue 6.0 May-07 41
Mnemonic
Scrolling Display and description
Range
MR
MANUAL RESET
applies to a PD only controller i.e. the integral term is
turned off. Set this to a value of power output (from +100% heat, to -
100% cool which removes any steady state error between SP and PV.
-100 to 100%
Default 0
R2G
RELATIVE COOL GAIN
adjusts the cooling proportional band relative to
the heating proportional band. Particularly necessary if the rate of
heating and rate of cooling are very different.
(Heat/Cool only
)
0.1
to 10.0
Default 1.0
HYST.H
HEATING HYSTERESIS
Sets the difference in temperature units
between heating turning off and turning on when ON’OFF control is
used.
Only appears if channel 1(heating) control action is On/Off
.
0.1
to 200.0 display units
Default 1.0
HYST.C
COOLING HYSTERESIS
Sets the difference in tempertaure units
between cooling turning off and turning on when ON/OFF control is
used.
Only appears if channel 2(cooling) control action is On/Off
.
0.1
to 200.0 display units
Default 1.0
D.BAND
CHANNEL 2 DEADBAND
Sets a zone between heating and cooling
outputs when neither output is on.
Off = no deadband. 100 = heating and cooling off.
Only appears if On/Off control configured.
OFF
or 0.1 to 100.0% of
the cooling proportional
band
OP.HI
OUTPUT HIGH
Sets the maximum heating power applied to the process
or the minimum cooling output.
+100% to OP.LO
Summary of Contents for 3200
Page 1: ...3200PID Temperature controllers User Guide Manuel Utilisateur Bedienungsanleitung ENG FRA GER ...
Page 57: ...3200Régulateurs de température PID Manuel Utilisateur FRA ...
Page 58: ......
Page 116: ...58 3200 Guide utilisateur HA028582FRA Indice 6 0 mai 07 ...
Page 117: ...3200PID Temperaturregler Bedienungsanleitung GER ...
Page 118: ......
Page 173: ......