42 Part number HA028582. Issue 6.0 May-07
Mnemonic
Scrolling Display and description
Range
1. (2, 3 or
4) PLS.
OUTPUT 1 (2, 3 or 4) MINIMUM PULSE TIME
Sets the minimum on
and off time for the control output.
!
Ensure this parameter is set to a value that is suitable for
the output switching device in use. For example, if a logic output
is used to switch a small relay, set the value to 5.0 seconds or
greater to prevent damage to the device due to rapid switching.
Relay outputs 0.1 to 150.0
seconds – default 5.0.
Logic outputs Auto to 150.0
-Default Auto = 55ms
This section applies to current transformer input.
If the CT option is not configured the parameters do not appear
LD.AMP
LOAD CURRENT
Is the measured load current when the output is on
CT Range
LK.AMP
LEAK CURRENT
Is the measured leakage current when output is off.
CT Range
LD.ALM
LOAD CURRENT THRESHOLD
Sets a low alarm on the load current
measured by the CT.
Used to detect partial load failure.
CT Range
LK.ALM
LEAK CURRENT THRESHOLD
Sets a high alarm on the leakage current
measured by the CT.
CT Range
HC.ALM
OVERCURRENT THRESHOLD
Sets a high alarm on the load current
measured by the CT
CT Range
ADDR
ADDRESS
- communications address of the controller. 1 to 254
1 to 254
Summary of Contents for 3200
Page 1: ...3200PID Temperature controllers User Guide Manuel Utilisateur Bedienungsanleitung ENG FRA GER ...
Page 57: ...3200Régulateurs de température PID Manuel Utilisateur FRA ...
Page 58: ......
Page 116: ...58 3200 Guide utilisateur HA028582FRA Indice 6 0 mai 07 ...
Page 117: ...3200PID Temperaturregler Bedienungsanleitung GER ...
Page 118: ......
Page 173: ......