Part number HA028582. Issue 6.0 May-07 7
1.3
Step 1: Installation
This controller is intended for permanent
installation, for indoor use only, and enclosed in an
electrical panel
Select a location which is subject to minimum
vibrations, the ambient temperature is within 0 and
55
o
C (32 - 131
o
F) and humidity 5 to 95% RH non
condensing.
The controller can be mounted on a panel up to
15mm thick
To ensure IP65 and NEMA 4 front sealing against
dust and water, mount on a non-textured surface.
Please read the safety information in section 3
before proceeding. The EMC Booklet part number
HA025464 gives further installation information.
1.3.1
Panel Mounting the Controller
1.
Prepare a cut-out in the mounting panel to the
size shown. If a number of controllers are to be
mounted in the same panel observe the
minimum spacing shown.
2.
Fit the IP65 sealing gasket behind the front
bezel of the controller
3.
Insert the controller through the cut-out
4.
Spring the panel retaining clips into place.
Secure the controller in position by holding it
level and pushing both retaining clips forward.
5.
Peel off the protective cover from the display
1.3.2
Panel Cut-out Sizes
.
45 mm
- 0.0 + 0.6
1.77 inch
-0.00, +0.02
92 mm
- 0.0 + 0.8
3.62 inch
-
0.00, +0.03
45 mm
- 0.0 + 0.6
1.77 inch
-0.00, +0.02
1/16 DIN Cut Out
1/8 DIN Cut Out
1/4 DIN Cut Out
92 mm
- 0.0 + 0.8
3.62 inch
-
0.00, +0.03
92 mm
- 0.0 + 0.8
3.62 inch
-0.00, +0.03
Summary of Contents for 3200
Page 1: ...3200PID Temperature controllers User Guide Manuel Utilisateur Bedienungsanleitung ENG FRA GER ...
Page 57: ...3200Régulateurs de température PID Manuel Utilisateur FRA ...
Page 58: ......
Page 116: ...58 3200 Guide utilisateur HA028582FRA Indice 6 0 mai 07 ...
Page 117: ...3200PID Temperaturregler Bedienungsanleitung GER ...
Page 118: ......
Page 173: ......