100 MM GRAPHICS RECORDER: USER GUIDE
HA027271
Issue 12 Mar 04
User Guide
Page 48
4.3.3 Channel/Alarm configuration
Figure 4.3.3a below, shows a typical configuration menu. The actual fields that appear depend on what input type is
selected, what linearisation type is selected, and so on.
Figure 4.3.3a Channel/alarm configuration menu (typical)
Notes
1.
Numeric values (e.g. 'input low') can be up to 10 characters including decimal point
2.
Refer to
for numeric and text entry techniques.
Apply
Discard
Channel Number
1) TurbineTempA
Select channel number
Input Type
Thermocouple
Select Linearisation
type (e.g.Type K)
Lin Type
Type K
Off, T/C, mV,V, mA,
RTD, Ohms, Digital,
Comms or Test
Range Low
0
C
Range High
1
C
Range Units
C
Scaled
Scale Low
0
V
Scale High
1
V
Select: Celsius, Fahrenheit, Kel-
vins or Rankine
Units
V
Offset
0
V
Filter
None
Select: None,
2, 4, 8, 16, 32, 64, 128 or 256
Break Response
None
Cold Junction Type
Off
Descriptor
TurbineTempA
Select: Off, Internal, External or Remote
Spanned
Span Low
0
V
Span High
1
V
Zone Low
0
%
Zone High
100
%
Max Decimal Digits
4
Colour
Alarm Number
1
Enable
Off
Job Number
1
Category
No Action
Select: Off,
Unlatched,
Latched,
Trigger
Select Job
action
26
Select: None, High or Low
18/04/02 15:17:10
5.003
Value
Scale Type
Scale Divisions - Major
Scale Divisions - Minor
Linear
5
1
Select: None, Linear or Log
(Log available only if Log Scales option fitted)
These fields vary with the
selected Scale Type.
PV Format
Numeric
A/B Switching
Select Numeric or Scientific
Select Alarm number