100/180 MM GRAPHICS RECORDER: USER GUIDE
User Guide
Page 79
HA261742
Issue 16 Nov 04
4.3.6 Event configuration
A number of internal and external (Event input option) triggers are available for use in initiating Events which will
then run job lists. Events can have up to two sources each, but can themselves be used as sources allowing a large
number of inputs to be used. Input sources can be logically combined, and can be inverted if required.
Figure 4.3.6 Event configuration menu layout (typical)
EVENT NUMBER
Allows the required event (1 to 96) to be selected for configuration.
SOURCE TYPES
Off
The event is disabled
Global alarm
The event is active whilst any one or more alarms is active
Global Unack'd alarm
The event is active as long as there is an unacknowledged alarm present.
Comms channel timeout
The event is set if no communication has been made with 'Comms' channels within the
Comms channel timeout period set in
(section 4.3.1). The
source is reset when the next communication occurs.
Timer active
The event is triggered when a specified timer becomes active (section 6 of the Options
Manual). If the Timers option is not fitted, 'Timer Active' does not appear in the picklist.
Batch Running
The event is triggered when a batch is started and remains active until the batch stops. If
Scope = 'Group' in Batch configuration (section 1.2 of the Options Manual) then a group
can be specified. If Scope = 'Instrument', the group select field does not appear. If the
Batch option is not fitted, 'Batch running' does not appear in the picklist.
Batch Start
The event is triggered, fleetingly, when a batch is started If Scope = 'Group' in Batch
configuration (section 1.2 of the Options Manual) then a group can be specified. If
Scope = 'Instrument', the group select field does not appear. If the Batch option is not
fitted, 'Batch running' does not appear in the picklist.
Event
Allows another event to be specified as a source.
Point alarm
Triggered by the specified alarm on the specified point.
Unack'd point alarm
Triggered by the specified alarm on the specified point. Remains active until the alarm is
acknowledged (
).
Alarm on Group
Triggered if any alarm in the specified group becomes active
Unack'd Alarm on Group
Triggered if any alarm in the specified group becomes active. The event remains active
until the alarm is acknowledged.
Apply
Discard
Select 1 to 96
Event Number
1) Event 1
Source 1
Descriptor
Event 1
Select job number
Job Number
1
Category
No Action
Select Job Category
Alarm on Group
Select source 1
On Group
1) Group 1
Source 2
Point Alarm
Select source 2
On
Math 12
Alarm
2
Source 1 Sense
Operator
Source 2 Sense
Source 1
And
Not Source 2
Make sub-sub selection (if any)
Select logic combination: Only, AND,
OR, NAND, NOR, XOR.
Select source inversion or not
Select source inversion or not
Make source 1 sub selection (if any)
Make source 2 sub selection (if any)