The function block protects the motor from
damage that may be caused by continuous
operation beyond specification.
)XQFWLRQDO
#
'HVFULSWLRQ
If the estimated load exceeds the STALL LIMIT for a time greater than STALL TIME then the
stall trip will become active. The timer is reset whenever the estimated load is less than the
STALL LIMIT.
Refer to Chapter 7 for a description of the trips supported by the Inverter.
00,
#
0HQX
#
0DS
4
SETUP PARAMETERS
5
FUNCTION BLOCKS
6
TRIPS
7
STALL TRIP
STALL LIMIT
STALL TIME
STALL TRIP
100.00 % – [240] STALL LIMIT
–
600.0 s – [241] STALL TIME
–
3DUDPHWHU
#
'HVFULSWLRQV
STALL LIMIT
Range: 50.00 to 150.00 %
The load limit beyond which the stall trip monitoring becomes active.
STALL TIME
Range: 0.1 to 3000.0 s
The time after which a stall condition will cause a trip.