Natural gas leak detection probe
Pre-heating time:
30s minimum
Alarms indication:
visual with 5 steps
5 alarms levels:
100, 200, 300, 400, 500 ppm
Acoustic Alarm indication:
respectively 1, 2, 3, 5 bip/s,
continuous
Response time:
5s (t90)
Alarm levels Accuracy:
±
10% at 90 days
Low Draft Probe
•
Range
:
±
200Pa
•
Resolution
: 0.1Pa
•
Operative temperature range
: from +5 to +45 °C
•
Accuracy
From +10 Pa to -10 Pa:
±
0.5 Pa
Elsewere:
±