18
DOWN UNDER
SERIES
It also shows the importance of correct wiring for vehicles, bigger is better and reduce the
number of connections between the battery and the fridge .
Cable Thickness (Area)
12V Max Cable Length
24V Max Cable Length
(mm
2
)
AWG
(m)
(ft)
(m)
(ft)
2 .5
13
2 .5
8
5
16
4
11
4
13
8
26
6
9
6
20
12
39
10
7
10
33
20
66
E2 Fan failure:
Probable cause – faulty fan
• Disconnect the fan from the module . Attach fan to a 12 Volt supply, if the fan does not
start it is a E2 fan error . Replace the fan .
• If the fan does start it will be an E2 Compressor protection error . This function was
introduced in 2015 by Secop to protect the new PCB compressors from multiple starts .
• Download the service bulletin here: https://www .evakool .com .au/SSP%20Applications/
NetSuite%20Inc .%20-%20SCA%202020 .1/Development/img/E2%20FAULT%20OR%20
COMPRESSOR%20PROTECTION
E3 Compressor start fault:
Probable cause - overheating, multiple starts, seized
compressor .
• This can occur if the fridge has trouble starting, unplug fridge let cool down for 30
minutes and start again .
• If you have a second module (that’s known to be good) try it on the compressor to
confirm if compressor is seized or not .
• Hot wire module to eliminate wiring and PCB issues see diagram below .
Summary of Contents for DOWN UNDER Series
Page 1: ...SERVICE MANUAL FOR MODEL DU47 SZ DOWN UNDER SERIES ...
Page 2: ......
Page 20: ...DOWN UNDER SERIES 20 5 Product Drawings DU47 SZ External Dimensions ...
Page 21: ...DOWN UNDER SERIES 21 DU47 SZ Wiring Display ...
Page 23: ......
Page 24: ...For Service and Warranty support contact Evakool T 1300 385 665 EVKOOL E warranty evakool com ...