16
Components (Continued)
Pressure Regulator Valve
The valve has been preset at the factory to 45 psi. Inlet supply pressure for your location may require field adjustment of the
regulator valve to achieve desired flow rate. This shall be discussed with the Factory Authorized Service Provider and approved
by EVAPCO to avoid damage to the system. Clean outlet flow rate directly correlates to inlet pressure and flow. Minimum inlet
pressure is 65 psi. Do not exceed 120 psi inlet pressure.
Water Meters
Meter is installed horizontally with register facing up. N/O reed switch set at 10 gallons per count is mounted on the dial face and
connected to the control panel.
Conductivity Probe
The EWS comes with an Inlet Conductivity Probe and an Outlet Conductivity Probe. See maintenance requirements in Table 4.
Panel Wiring Locations
In Figure 17, Valve Connections refer to the “Flush Output” and “Clean Output” solenoid valves. Sensor Connections refer to the
Inlet and Outlet Conductivity Probes, the Water Pressure Sensor, and the Inlet Flow Meter.
Figure 17: Inside Panel Wiring
Valve Connections
Sensor Connections