Notice on installation
Installation advice
Ground
TN-system
PE-cable
TT-system
IT-system
Earth electrode installed
separately (to be installed)
Input
1-phase
230 V ± 10 %, 50 Hz
3-phase
400 V ± 10 %, 50 Hz
MCB
C-characteristic (MCB must be selected to match the
amperage settings of the wallbox, considering MCB
manufacturer specifications)
RCD
40 A, 30 mA, AC Type A
For a TT or IT electric grid with 230
V from line to line, the wallbox must be
installed with one phase being connected
to clamp L1 and the other phase being
connected to clamp N.
Make sure that the provided ground
connection meets the local regulations.
The ground loss monitor functionality of
the wallbox is limited to physical ground
loss detection and cannot detect quality.
English
Warning
Connecting the wallbox to the power supply other than as specified in this section could
result in incompatibility of the installation as well as the risk of electric shock, which could
cause damage to the wallbox, and injury or death.
› Only connect the wallbox to a power supply in a configuration that is specified in this
section. (see Option 1, 2 and 3)