EVLJBOX HP Sequencer -
Application manual
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
PG02
Number of slaves in stand-by
0
0
PG01
IS-CF
PG03
Enable evaporator mixing valve
NO (0)
NO (0)
YES (1)
IS-CF
PG04
Enable condenser mixing valve
NO (0)
NO (0)
YES (1)
IS-CF
Regulation
Pr01
Regulation neutral zone
3.0
0.1
20.0
°C
IS-R
Pr02
Percentage increase/decrease of
regulation
5
0
100
%
IS-R
Pr03
Time increase/decrease of regulation
5
1
100
Sec
IS-R
Pr04
Slave rotation time
10
0
255
Hours
IS-R
Pr05
Inversion mixing valves inputs/outputs in
heating mode:
0: Inputs only
1: Outputs only
2: Inputs/Outputs
0
0
2
IS-R
Evaporator mixing valve
PE01
Evaporator valve regulation probe:
0: T. input
1: T. output
0
0
1
IS-E
PE02
Evaporator valve heating setpoint
30.0
0.0
70.0
°C
IS-E
PE03
Evaporator valve heating differential
10.0
0.1
20.0
°C
IS-E
PE04
Evaporator valve integral heating time
0
0
999
Sec
IS-E
PE05
Evaporator valve minimum opening
(output activation step)
0
0
PE06
%
IS-E
PE06
Evaporator valve maximum opening
100
PE05
100
%
IS-E
PE07
Evaporator valve polarity:
0: 0-10 V
1: 10-0 V
0
0
1
IS-E
PE08
Evaporator valve cooling differential
10.0
0.1
20.0
°C
IS-E
PE09
Evaporator valve integral cooling time
0
0
999
Sec
IS-E
PE10
Kind of regulation evaporator valve
0: Minimum ON
1: Enabling step
0
0
1
IS-E
Condenser mixing valve
PC01
Condenser valve regulation probe:
0: T. input
1: T. output
0
0
1
IS-CO
PC02
Condenser valve cooling setpoint
30.0
0.0
70.0
°C
IS-CO
PC03
Condenser valve cooling differential
10.0
0.1
20.0
°C
IS-CO
PC04
Condenser valve integral cooling time
0
0
999
Sec
IS-CO
PC05
Condenser valve minimum opening
(output activation step)
0
0
PC06
%
IS-CO
PC06
Condenser valve maximum opening
100
PC05
100
%
IS-CO
PC07
Condenser valve polarity:
0: 0-10 V
1: 10-0 V
0
0
1
IS-CO
PC08
Condenser valve heating differential
10.0
0.1
20.0
°C
IS-CO
PC09
Condenser valve integral heating time
0
0
999
Sec
IS-CO