EVLJBOX HP Sequencer -
Application manual
Code
CHILLER
AL06
Source flow switch
AL83
Source antifreeze circuit 1
AL84
Source antifreeze circuit 2
EVM1
EVCM circuit 1
EVM2
EVCM circuit 2
AL07
Phase sequence
AL08
Water level
Slave configuration alarm
When the application in the slaves or the type of condenser are not the same for all the configured slaves, the slave
configuration alarm will be signalled
AL01
.
This alarm can be set off when HPRU slaves and CHILLER slaves are connected in the same network or when different types
of condenser have been configured in the same network (as in the case of slaves with an air condenser together with slaves
with a water condenser).
This alarm will be bypassed when switching on and after a 60 second re-arm to enable all the MODBUS registers in the
network to be correctly read.
The consequences of manual re-arm alarm are:
–
Inhibition of temperature regulation
–
Inhibition of MODBUS communication with the slaves
Slave communication alarm
When the sequencer does not receive a response from the slave for more than 60 seconds, the slave communication alarm
will be signalled (
AL02..AL06
according to the slave).
This is an automatic re-arm alarm and will inhibit the sequencer from regulating the same slave.