EVCO S.p.A.
Vcolor 869/879
| Installer manual ver. 2.2 | Code 144VC869E214
page 35 of 94
-
The sensor showing the highest temperature is then used as the reference point for the end of the
temperature controlled cycles.
-
Any sensors for which the test is not completed with a successful outcome are not subsequently used.
If the test fails to record a positive outcome, that is to say the needle probe is not inserted, the buzzer sounds and the
cycle automatically changes to time-controlled or keeps on as a temperature-based cycle, depending on how parameter
E14 is set.
7.6.2
Recording historical data
While a cycle is in progress records are kept of the temperature values of any probes enabled, output activations, input
status, defrosting cycles carried out and any alarms.
The type of data to be recorded can be set using the menu accessible from the service area, see section 12.1.
These data are available for subsequent download to a USB device, see section 13.4.
7.6.3
Cycle end
If the temperature controlled blast chilling/blast-freezing cycle is successfully completed, in which the centre of the
product reaches the required temperature in the allotted time, the device moves on automatically to the conservation
phase, with the following screen appearing.
If the temperature controlled cycle is not completed in the allotted time, this problem will be signalled by the appearance
of the alarm icon, but the blast chilling cycle will still continue.
In temperature controlled cycles, pressing the
key will bring up the screen granting access to the following
functions.
heat needle probe to remove it from the product;
record the cycle just performed in the memory.