EVCO S.p.A.
Vcolor 869/879
| Installer manual ver. 2.2 | Code 144VC869E214
page 74 of 94
A10
5
0
240
min
Power failure duration sufficient for the power failure alarm to be
saved (“
POWER FAILURE
” code) when this is restored
0 = the alarm will not be signalled
A11
2
1
15
°C/°F
(1)
Parameter A1 and A4 differential
A12
5
0
240
s
Duration of buzzer activation on completion of blast chilling and
blast-freezing.
A13
60
0
240
s
Duration of buzzer activation for an alarm event
PAR.
DEFAULT
MIN.
MAX.
U.M.
EVAPORATOR AND CONDENSER FANS
F1
-1
-50
99
°C/°F
(1)
The evaporator temperature above which the evaporator fan
switches
off
during
pre-cooling/blast
chilling/blast-
freezing/sanitation/ice cream hardening/blast chilling (for
proofing cycle). See also parameter F8.
F3
2
0
15
min
Duration of evaporator fan-off time (while the evaporator fan is
off the compressor may be switched on, the defrost output is de-
activated and the evaporator fan stays off).
F8
2
1
15
°C/°F
(1)
Parameter F1 and F17 differential.
F15
15
0
240
s
Evaporator fan delay from when the door is closed, or the door
switch input is deactivated.
F17
90
-50
199
°C/°F
(1)
Cabinet temperature above which the evaporator fan is
switched off during pre-cooling/blast chilling/blast-
freezing/sanitation/ice cream hardening/blast chilling (for
proofing cycle). See also parameter F8.
F19
20
0
100
%
Evaporator fan minimum speed calibration.
F20
80
0
100
%
Evaporator fan maximum speed calibration.
F21
80
0
100
%
Start-up speed.
F22
5
0
10
s
Start-up time.
F23
5
1
5
- - - -
Fan speed during blast chilling and soft blast-freezing phase.
F24
5
1
5
- - - -
Fan speed during hard blast chilling phase.
F25
5
1
5
- - - -
Fan speed during blast-freezing and ice cream hardening.
F26
5
1
5
- - - -
Fan speed during positive conservation.
F27
5
1
5
- - - -
Fan speed during negative conservation.
F28
5
1
5
- - - -
Fan speed during pre-cooling.
F29
1
1
5
- - - -
Fan speed in first thawing phase.
F30
1
1
5
- - - -
Fan speed in second thawing phase.
F31
1
1
5
- - - -
Fan speed in third thawing phase.
F32
1
1
5
- - - -
Fan speed in fourth thawing phase.
F33
1
1
5
- - - -
Fan speed in fifth thawing phase.
F34
1
1
5
- - - -
Fan speed during conservation after thawing.