EVCO S.p.A.
Vcolor 869/879
| Installer manual ver. 2.2 | Code 144VC869E214
page 79 of 94
E9
1
0
1
- - - -
Display EVCO splash screen when power is restored
0 = no
1 = yes
E10
0
0
1
- - - -
Humidifying/steam generator heater management mode
0 = output is always active in the cycles for which humidifying
is required
1 = output is active until reaching the cabinet setpoint of the
cycle in progress for which humidifying is required. This
function will be reactivated when the temperature drops
below the setpoint by at least 5°C.
E12
0
0
3
- - - -
Enable expansion module functions
0 = no
1 = only slow cooking
2 = only retarding proofing
3 = slow c retarding proofing
NB:
when changing this parameter, the device will be
automatically restarted.
E13
0
0
1
- - - -
Machine type
0 = Home “blast chiller”
1 = Home “multifunction”
NB:
when changing this parameter, the device will be
automatically restarted.
E14
0
1
0
- - - -
Operating mode when needle probe insertion test fails
0 = time-controlled
1 = needle probe
E15
0
1
0
- - - -
Save modified OEM recipes
0 = in the user recipe book
1 = in the user recipe book + overwrite OEM recipe
E16
0
1
1
- - - -
Ventilation mode
0 = with phase cutting
1 = without phase cutting
E17
0
0
1
- - - -
type of sterilization
0 = UV lamp
1 = ionizer
E18
0
0
2
- - - -
ionizer state transition from cycle to cold storage
0 = keep previous status
1 = off
2 = on
E19
60
0
240
min
ionizer operation time-out in cold storage
Notes
(1)
the unit of measurement depends on parameter P2