EVCO S.p.A.
Vcolor 869/879
| Installer manual ver. 2.2 | Code 144VC869E214
page 84 of 94
COMPRESSOR
LOCKED
Compressor locked alarm.
To correct
-
Check the condenser temperature
-
Check the value of parameter C7
-
Disconnect the device from the power supply and clean the condenser.
Main consequences
-
If the error happens during “stand-by”, it will not be possible to select or start up an
operating cycle.
-
If the error happens during an operating cycle, the cycle will be interrupted.
-
The alarm output will be activated.
NEEDLE PROBE
INSERTION
Needle probe not inserted alarm.
To correct
-
Check that the needle probes have been correctly inserted and check the value of
parameters r17 and r18.
Main consequences
-
The temperature controlled cycle in progress will be converted to a time controlled cycle.
EXPANSION
COMMUNICATIO
NS
User interface-expansion module communication error.
To correct
-
Check the user interface-expansion module connection.
Main consequences
-
Any proofing or slow cooking cycle underway will be terminated and it will not be possible
to start one up.
EXPANSION
COMPATIBILITY
User interface–expansion module compatibility error.
To correct
- Check the user interface and expansion module are compatible.
Main consequences
- Any cycle underway will be terminated and it will not be possible to start one up.