EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
Type 01 2019-06-10 14:36
Technical Assistance, phone: +48 61 6500 400
20
Table 5. List of settings sub-menu parameters
Sub-menu
Name
Parameter name
Description
Date & Time
Date format setting
The date can be displayed in of three formats:
a) year/month/day, b) month/day/year
c) day/month/year
Time setting
Current time setting
Language
Selected language
The current language of the UPS unit's menu
Language selection
The following menu languages can be set:
English, Portuguese, Italian, Polish, Turkish,
Chinese. To change the language press the
corresponding icon.
COMM.
Device’s address
Communication port setting
RS232 protocol selection
SNT Protocol, Modbus Protocol,
Baud rate
Setting the baud rate of SNT, Modbus
Modbus mode
Setting mode for Modbus: ASCII and RTU
selectable
USER
PIN: 1203
Output voltage
Setting the output voltage value
Upper limit for the bypass
line
Setting the upper limit for the bypass line.
Available selection: +10%
,
+15%
,
+20%
,
+25%
Bottom limit for the bypass
line
Setting the bottom limit for the bypass line.
Available selection
Frequency tolerance for
the bypass line
Setting the voltage frequency tolerance for the
bypass line. Available selection: +/-1Hz
,
+/-3Hz
,
+/-5Hz.
BATTERY
No. of batteries
Setting the number of batteries
(
12V
)
Battery capacity
Entering the capacity of the used batteries (Ah)
Charging voltage in float
mode
Setting the charging voltage in float mode
(voltage / battery cell)
(
2V
)
Charging voltage in boost
mode
Setting the charging voltage in boost mode
(voltage / battery cell)
(
2V
)
Charging current
Setting the battery charging current (percentage
of the rated current)
SERVICE
UPS operating mode
Setting the system mode: Single, parallel, Single
ECO,
UPS unit's number in
parallel operation
Parallel system UPS numbers
UPS unit's ID in parallel
operation
UPS ID in parallel system
Slew rate
Bypass frequency slew rate
Synchronization range
Bypass frequency slew window
Auto restart after the
batteries are discharged
Automatic restart of the UPS after the power
supply is back, following the earlier discharge
(while operating in battery mode)
RATE
Setting the UPS unit's
rated parameters
Option available only for service technicians.
CONFIGURE
Display mode
Support Tower and Rack LCD display
Backlight level
LCD display backlight brightness level
Contrast
LCD display contract level