EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
37
Technical Assistance, phone: +48 61 6500 400
2019-06-10 14:36 Type 01
11. Start the device following the start-up procedure.
Disconnecting battery modules
1. Switch the UPS off in the user interface.
2.
Switch the UPS unit’s input protection (of the basic line and the bypass line) to
OFF.
3. Disconnect the protections of the basic line and the bypass line i
n the room’s /
building's switching board.
4. Switch the DC protection (in the rear panel) to OFF.
5. Disconnect the battery protections in all battery modules by opening the fuse
housing and removing the fuse elements.
6. Remove the covers of connecting elements.
7. Disconnect the modules. The connecting leads must be completely disconnected.
8. Secure the connecting elements by installing protective covers.
9.
Switch the protections in the room's / building’s switching board.
10. Start the device following the start-up procedure.
CAUTION!
No disconnected leads may be left. These leads may be live
with voltage that is dangerous to health and life.